Lochinvar 495 Connecting To Electrical Supply, Low Water Cutoff, Relief Valve, Water Flow Switch

Models: 000 - 2 065 495

1 52
Download 52 pages 31.23 Kb
Page 21
Image 21
Low Water Cutoff

Installation and Service Manual

Low Water Cutoff

(If Equipped)

If installing this unit above radiation level, you must install a low water cut-off device at the time of appliance installation. Electronic or float type low water cutoff controls are available as a factory supplied option on all units. Inspect the low water cutoff every six months, including flushing of float types. The low water cutoff control is located on the control panel directly behind the control panel cover.

The reset and test buttons (if equipped) are located on the control panel.

Figure 22 - Water Connections

Relief Valve

This unit is supplied with a relief valve(s) sized in accordance with ASME Boiler and Pressure Vessel Code, Section IV ("Heating Boilers"). The relief valve(s) is installed in the vertical position and mounted in the hot water outlet. Place no other valve between the relief valve and the unit. To prevent water damage, pipe the discharge from the relief valve to a suitable floor drain for disposal when relief occurs. Do not install any reducing couplings or other restrictions in the discharge line. The discharge line will allow complete drainage of the valve and line. Manually operate the relief valves at least once a year.

￿CAUTION: Avoid contact with hot discharge water.

Water Flow Switch

A water flow switch is factory installed. The flow switch is wired in series with the 24 VAC safety control circuit at the units terminal strip. This wiring connection installs the flow switch in the 24 VAC safety circuit to prove water flow before main burner ignition. The factory supplied flow switch is installed in the outlet side of the front header. These units require a minimum flow of 26 GPM to make the flow switch and start burner operation. Ensure that the pump installed on the unit will supply adequate flow to make the flow switch contacts and operate the unit. A water flow switch meets most code requirements for a low water cut off device on appliances requiring forced circulation for operation.

CONNECTING TO ELECTRICAL SUPPLY

This unit is wired for 120 VAC service. The unit, when installed, must be electrically grounded in accordance with the requirements of the authority having jurisdiction or in the absence of such requirements, with the latest edition of the National Electrical Code ANSI/NFPA No. 70. When the unit is installed in Canada, it must conform to the CAE C22.1, Canadian Electrical Code, Part 1 and/or local Electrical Codes.

1.Use only Type-T wire [63°F (35°C) rise] on all wiring between the unit and field-installed devices.

2.Enclose line voltage wire exterior to the unit in approved conduit or approved metal-clad cable.

3.The pump must run continuously when the unit is being fired (hot water heating boilers must use the optional pump delay if the pump is to be cycled. See Freeze Protection, page 7 when cycling the pump). Water heaters use the pump delay as standard in accordance with ASHRAE 90.1 requirements.

4.To avoid serious damage, do not energize the unit until the system is filled with water.

5.Provide the unit with proper overload protection.

21

Page 21
Image 21
Lochinvar 495, 065, 000 - 2 Connecting To Electrical Supply, Low Water Cutoff, Relief Valve, Water Flow Switch, If Equipped