Lochinvar 800 Near boiler piping connections, Flow switch adjustment, Circulator sizing

Models: 800

1 76
Download 76 pages 56.19 Kb
Page 36
Image 36

Installation & Operation Manual

6Hydronic piping

Flow switch adjustment

Refer to Table 6A for the proper setting of the sensitivity screw. For reference, the position of the screw prior to setting should be turned clockwise with a Phillips driver until it stops (FIG. 6-3). Proceed to turn the screw counterclockwise the amount of turns listed in Table 6A based on the model.

Consult the manufacturer’s instructions for wiring the flow switch to your system.

Table 6A Paddle Size / Sensitivity Screw Adjustment

MODEL

PADDLE SIZE

SENSITIVITY SCREW

ADJUSTMENT

 

 

 

 

 

Note: Paddles are included with the flow switch.

399

#3

7½ turns

500

#3

5½ turns

600

#3

7¼ turns

700

#3

5¼ turns

800

#3

3¼ turns

Near boiler piping connections

Figure 6-4ANear Boiler Piping w/Y-Strainer

SYSTEM

FROM

 

 

DOMESTIC HOT

SYSTEM PUMP

WATER PUMP

INDIRECT

 

DOMESTIC

 

 

 

 

 

FROM HOT WATER

 

SYSTEM

TO

TANK

TO

 

 

 

 

 

 

BOILER PUMP

 

 

 

Y-STRAINER

 

 

 

(RECOMMENDED)

 

 

NOTICE

Turn the sensitivity screw clockwise to increase the flow rate required to activate the switch. Turn the sensitivity screw counterclockwise to decrease the flow rate required to activate the switch.

Figure 6-3Flow Switch Adjustment

NORMALLY

OPEN

SENSITIVITY

ADJUSTMENT

TO FLOOR

DRAIN

Figure 6-4BNear Boiler Piping w/Low Loss Header

GROUND

COMMON NORMALLY

CLOSED

Circulator sizing

SYSTEM PUMP

SYSTEM SENSOR

AIR SEPARATOR

DRAIN

(TYPICAL)

AIR VENT VALVE LOW LOSS HEADER (TYPICAL)

TO

SYSTEM

 

SYSTEM

FROM

 

EXPANSION TANK

FAST FILL VALVE

INDIRECT

 

DRAIN VALVE

DOMESTIC

FROM HOT WATER

TO

TANK

The Knight XL heat exchanger does have a pressure drop, which must be considered in your system design. Refer to the graphs in FIG’s 6-5 and 6-6 for pressure drop through the Knight XL heat exchanger.

36

Y-STRAINER (RECOMMENDED)

TO FLOOR

DRAIN

Page 36
Image 36
Lochinvar 800 operation manual Near boiler piping connections, Flow switch adjustment, Circulator sizing