11 Operating information (continued)

Status Display Screens

By using the Previous/Next (￿, ￿) arrow keys on the SMART SYSTEM display panel, you can navigate through the eight (8) display screens. Each screen will contain two (2) viewable items. The following is a description of the individual items and what they can display:

Screen

 

Display shows:

Description

 

 

BLR: OFF

The unit has been turned OFF by the Enter/Reset button on the

 

 

SMART SYSTEM display panel.

 

 

 

 

 

 

 

 

 

Standby

The unit has not received a call for heat from a remote thermostat nor

 

 

has it received a call for heat from a DHW thermostat.

 

 

 

 

 

 

 

 

 

Set Point Met

The unit has met the water temperature set point, but is still receiving

 

 

a call for heat from either a remote thermostat or a DHW thermostat.

 

 

 

 

 

 

 

 

 

 

The unit has initiated a 10 second purge period on a call for heat.

 

 

Prepurge

Note: On the 800 model the unit will initiate a 20 second purge

 

 

 

period on a call for heat.

 

 

 

 

 

 

Ignition

The unit has begun a 5 second spark period to ignite the main burner.

 

 

 

 

#1

 

SH***% Rate

The unit has fired and is running at the displayed percentage.

 

 

 

 

 

The call for heat has been satisfied and the unit runs the fan for an

 

 

 

 

 

Postpurge

additional 10 seconds to clear the combustion chamber and vent

 

 

 

system of residual flue products.

 

 

 

 

 

 

Service

The unit has been placed in a temporary mode that will allow the unit

 

 

to fire at 100% of rate for the purpose of combustion analysis.

 

 

 

 

 

 

 

 

 

 

When the outlet sensor has been selected as the control sensor

 

 

OUT: ***.*F(***)

(default), the control will display the outlet temperature as well as the

 

 

 

set point in parenthesis.

 

 

 

 

 

 

***.*F

If the outlet sensor has not been selected as the control sensor, only

 

 

the outlet temperature will be displayed.

 

 

 

 

 

 

 

 

 

Open

The control does not detect the outlet sensor.

 

 

 

 

 

 

Shorted

The outlet sensor wires or the sensor itself has become shorted.

 

 

 

 

 

Press

the Next ￿ arrow key on the

SMART SYSTEM display to access Screen #2.

 

 

IN: ***.*F

If the inlet sensor has not been selected as the control sensor, only the

 

 

inlet temperature will be displayed.

 

 

 

 

 

 

 

 

 

 

When the inlet sensor has been selected as the control sensor, the

 

 

***.*F (***)

control will display the inlet temperature as well as the set point in

#2

 

 

parenthesis.

 

 

 

 

 

Open

The control does not detect the inlet sensor.

 

 

 

 

 

 

Shorted

The inlet sensor wires or the sensor itself has become shorted.

 

 

 

 

 

 

RISE: ***.*F

The difference between the inlet temperature and the outlet

 

 

temperature.

 

 

 

 

 

 

 

 

Press

the Next ￿ arrow key on the

SMART SYSTEM display to access Screen #3.

 

 

 

 

63

Page 63
Image 63
Lochinvar 800 Standby, Set Point Met, Prepurge, Ignition, SH***% Rate, Postpurge, Service, Out ***.*F, Open, Shorted

800 specifications

Lochinvar 800 is a groundbreaking boiler system designed to meet the heating needs of modern residential and commercial buildings. Renowned for its reliability and advanced technology, the Lochinvar 800 promises efficiency and performance that set it apart from conventional heating systems.

One of the standout features of the Lochinvar 800 is its high-efficiency heat exchanger, which enables significantly lower energy consumption compared to traditional units. This efficiency translates to substantial energy savings, making it not only an environmentally friendly choice but also a cost-effective one. The system boasts an impressive thermal efficiency rating, often exceeding 95%, which ensures that a large portion of the energy consumed is converted into usable heat.

Incorporating cutting-edge control technologies, the Lochinvar 800 utilizes smart controls that enable precise temperature regulation. These controls provide users with the ability to program and adjust settings according to specific heating needs, enhancing comfort while minimizing energy waste. The integration of modulating gas burners further optimizes energy usage, continuously adjusting the output based on the current demand, thereby preventing energy loss.

Another key characteristic of the Lochinvar 800 is its compact and sleek design, allowing for easy installation in various spaces, from utility rooms to commercial settings. The boiler's lightweight construction means that it can be mounted in tight areas, providing flexibility that adapts to the needs of the installation site.

Safety features are a top priority for the Lochinvar 800, equipped with advanced diagnostics and monitoring systems that ensure trouble-free operation. These systems continually assess performance and identify potential issues before they can evolve into serious problems, promoting longevity and reliability.

The Lochinvar 800 is also compatible with various heating distribution systems, including radiant floor heating and traditional radiators, making it a versatile choice for a wide range of applications. Coupled with its low emissions profile, the Lochinvar 800 stands out as a sustainable option in today’s market.

In summary, the Lochinvar 800 represents a new era in boiler design, merging efficiency, innovative technology, and adaptability to meet the challenges of contemporary heating needs. Its advanced features ensure optimal performance while maintaining a commitment to environmental responsibility, making it an ideal solution for energy-conscious consumers.