11 Operating information

Status Display Screens (cont’d)

Operation of the cascade

The boiler designated as the Leader will have two additional display screens that can be viewed. These screens will provide information regarding the operation of the Cascade. Each screen will contain two viewable items. The following is a description of the individual items and what they can display:

Screen

 

Display shows:

Description

 

 

Cas: Off

The Leader control has been turned off by the Enter/Reset button on

 

 

the Smart System display.

 

 

 

 

 

 

 

 

 

Cas: Standby

The Leader boiler has not received a call for heat from a remote

 

 

thermostat.

 

 

 

 

 

 

 

 

 

Cas: 127.4F (130)

The Cascade is now active. The system supply temperature will be

 

 

displayed. The Cascade set point will be displayed in parenthesis.

 

 

 

 

 

 

 

 

 

Cas: Setpoint Met

The Cascade has met the water temperature set point, but is still

 

 

receiving a call for heat from a remote thermostat.

 

 

 

 

 

 

 

 

 

Cas: No Members

The Leader control could not detect any Member controls to

#9

 

participate in the Cascade.

 

 

 

 

 

 

 

 

Cas: S6 Not Present

The system supply sensor is not connected to the Leader boiler.

 

 

 

 

 

 

PMP: Off

The Leader control has not received a call for heat from a remote

 

 

thermostat and has not powered the system pump.

 

 

 

 

 

 

 

 

 

PMP: On

The Leader control has received a call for heat from a remote

 

 

thermostat and has powered the system pump.

 

 

 

 

 

 

 

 

 

PMP: Delay

The system call for heat has been satisfied and the system pump is

 

 

running for a fixed time to remove any residual heat.

 

 

 

 

 

 

 

 

Press the Next ￿ arrow key on the SMART SYSTEM display to access Screen #10.

 

 

 

 

#10

 

The first percentage shows the firing rate that is being sent to the last

Cas Pow: ***% ***%

boiler called on. The second percentage shows the total power

 

available to the Cascade.

 

 

 

Shows the number of boilers connected to the Cascade. The Leader is

 

designated as 0. Members will be designated 1 - 7. If a “-“ is used in

Present: 01234567

place of a number, that boiler is either not connected, or in a lockout

mode and not available for the Cascade. If a “d” is used in place of a

 

Example:

number, that boiler is handling a DHW demand and is not available

for the Cascade. If the number is flashing, then that boiler is providing

Present: 23----d1

heat to the Cascade. As the lead boiler is changed from day to day, that

 

 

boiler’s address will be shown first in the string of numbers. In the

 

example, boilers 0 - 3 are present, boiler 2 is the lead boiler, and boiler

 

0 is heating an indirect DHW tank.

Press the Next ￿ arrow key on the SMART SYSTEM display to roll back to Screen #1. At any point if you wish to access an earlier screen, press the Previous ￿ arrow key on the SMART SYSTEM display.

66

Page 66
Image 66
Lochinvar 800 operation manual Operation of the cascade

800 specifications

Lochinvar 800 is a groundbreaking boiler system designed to meet the heating needs of modern residential and commercial buildings. Renowned for its reliability and advanced technology, the Lochinvar 800 promises efficiency and performance that set it apart from conventional heating systems.

One of the standout features of the Lochinvar 800 is its high-efficiency heat exchanger, which enables significantly lower energy consumption compared to traditional units. This efficiency translates to substantial energy savings, making it not only an environmentally friendly choice but also a cost-effective one. The system boasts an impressive thermal efficiency rating, often exceeding 95%, which ensures that a large portion of the energy consumed is converted into usable heat.

Incorporating cutting-edge control technologies, the Lochinvar 800 utilizes smart controls that enable precise temperature regulation. These controls provide users with the ability to program and adjust settings according to specific heating needs, enhancing comfort while minimizing energy waste. The integration of modulating gas burners further optimizes energy usage, continuously adjusting the output based on the current demand, thereby preventing energy loss.

Another key characteristic of the Lochinvar 800 is its compact and sleek design, allowing for easy installation in various spaces, from utility rooms to commercial settings. The boiler's lightweight construction means that it can be mounted in tight areas, providing flexibility that adapts to the needs of the installation site.

Safety features are a top priority for the Lochinvar 800, equipped with advanced diagnostics and monitoring systems that ensure trouble-free operation. These systems continually assess performance and identify potential issues before they can evolve into serious problems, promoting longevity and reliability.

The Lochinvar 800 is also compatible with various heating distribution systems, including radiant floor heating and traditional radiators, making it a versatile choice for a wide range of applications. Coupled with its low emissions profile, the Lochinvar 800 stands out as a sustainable option in today’s market.

In summary, the Lochinvar 800 represents a new era in boiler design, merging efficiency, innovative technology, and adaptability to meet the challenges of contemporary heating needs. Its advanced features ensure optimal performance while maintaining a commitment to environmental responsibility, making it an ideal solution for energy-conscious consumers.