INSTALLATION Continued

Table - O

LTV Valve Kits

Input

LTV Valve Kit

Btu/hr

399,999 - 750,000VAL3048

990,000 - 2,070,000 VAL3047

 

 

 

 

 

 

 

 

 

 

 

Be sure to install the LTV valve per the piping diagrams

 

 

 

 

 

 

 

 

 

 

 

included with the kits. Alternatively, a bypass as shown in

 

 

 

 

 

 

 

 

 

 

 

FIG. 38 may be piped into the system. This piping is like a

 

 

 

 

 

 

 

 

 

 

 

primary/secondary boiler installation with a bypass in the

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

secondary boiler piping. Inlet water temperatures below 140°F

 

 

 

 

 

 

 

 

 

 

 

(60°C) can excessively cool the products of combustion

 

 

 

 

 

 

 

 

 

 

 

resulting in condensation on the heat exchanger and in the flue.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Condensation can cause operational problems, bad

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

combustion, sooting, flue gas spillage and reduced service life

 

 

 

 

 

 

 

 

 

 

 

of the vent system and related components. The bypass allows

FIG. 36 Primary/Secondary Piping of a Single Boiler

part of the boiler discharge water to be mixed with the cooler

boiler return water to increase the boiler inlet temperature

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

above 140°F (60°C). This should prevent the products of

 

 

 

 

 

 

 

 

 

 

 

combustion from condensing in most installations. The bypass

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

should be fully sized with a balancing valve to allow for proper

 

 

 

 

 

 

 

 

 

 

 

adjustment. A valve must also be provided on the boiler

 

 

 

 

 

 

 

 

 

 

 

discharge, after the bypass. Closing this discharge valve forces

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

water through the bypass. Start boiler adjustment with the

 

 

 

 

 

 

 

 

 

 

 

bypass valve in the full open position and the boiler discharge

 

 

 

 

 

 

 

 

 

 

 

valve half open. A small amount of the higher temperature

 

 

 

 

 

 

 

 

 

 

 

boiler discharge water is mixed with the system water to

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

maintain the desired lower system temperature. A remote low

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

temperature range operator is recommended to control the

 

 

 

 

 

 

 

 

 

 

 

boiler operation based on the lower system temperature. (See

 

 

 

 

 

 

 

 

 

 

 

Terminal Strip Connection Options starting on

 

 

 

 

 

 

 

 

 

 

 

page 40).

FIG. 37 Primary/Secondary Piping of Multiple Boilers

Low Temperature Return Water

Systems

Any non-condensing boiler and venting system will develop operational problems when exposed to inlet water temperatures below 140°F. Lochinvar offers a low temperature protection valve (LTV) that is factory preset to

maintain 140°F inlet water to the boiler regardless of the FIG. 38 Boiler with Low Temperature Bypass Piping system return water temperature. See Table O for available

valve kits.