Lochinvar 999 - 750 Heat Exchanger Cleaning, Electrical, Combustion and Ventilation Air, Air Flow

Models: 399 CF-CH(E)-i&s-08 999 - 750

1 72
Download 72 pages 15.81 Kb
Page 57
Image 57

Installation and Service Manual

Heat Exchanger Cleaning

1.While burners are removed, check the heat exchanger surface for sooting. If present, heat exchanger must be cleaned and problem corrected. Proceed as follows.

2.Remove gas manifold(s)/orifice assemblies as described in steps 1 through 5 in Burner Removal and Cleaning, page 56.

3.Disconnect wiring from hot surface igniter(s) and hoses from burner pressure taps.

4.Remove inner jacket panel mounting screws and slide door assembly out toward front of the unit. Use caution to prevent damage to the refractory and hot surface igniters.

5.Check “V” baffles and frame runners along front and back edges of heat exchanger. Remove and clean if necessary.

6.Remove soot from heat exchanger with a stiff bristle brush. Use a vacuum to remove loose soot from surfaces and inner chamber.

7.The heat exchanger can be removed by sliding towards the front of the unit. Once the heat exchanger is removed from the unit, a garden hose can be used to wash the tubes to ensure that all soot is removed from the heat exchanger surfaces. Note: Do not wet the unit’s refractory.

8.Ensure that all burner ports are cleaned to remove any soot. See Burner Removal and Cleaning, page 56.

9.Carefully reinstall the heat exchanger, “V” baffles, and frame runners if removed from the unit. Note: Make sure frame runners seal securely where they contact the front and rear compartment refractory.

10.Carefully reinstall inner jacket panels, burners, manifolds, wires and hoses. Use new gasket material to ensure a proper air seal.

11.Reassemble all gas and water piping. Test for gas leaks.

12.Reassemble outer jacket panels.

13.Cycle unit and check for proper operation.

Electrical

This unit uses a transformer to supply a low voltage control circuit. The voltage on the secondary side should be 24 to 28 VAC when measured with a volt meter. The 399,999 - 750,000 Btu/hr models have a 5 AMP circuit breaker provided on the secondary side of the transformer and the 990,000 - 2,070,000 Btu/hr models have a 7 AMP circuit breaker provided on the secondary side of the transformer. A tripped circuit breaker indicates a short in the 24VAC controls that must be corrected.

Combustion and Ventilation Air

Combustion Air Filter

This unit has a standard air filter located at the combustion air inlet. This filter helps ensure clean air is used for the combustion process. Check this filter every month and replace when it becomes dirty. The filter size on the 399,999 - 750,000 Btu/hr models is 12" x 12" x 1" (30.5cm x 30.5cm x 2.5cm) and 16" x 16" x 1" (40.6cm x 40.6cm x 2.5cm) on the 990,000

-2,070,000 Btu/hr models. You can find these commercially available filters at any home center or HVAC supply store.

Venting System

Examine the venting system at least once a year. Check more often in the first year to determine inspection interval. Check all joints and pipe connections for tightness, corrosion or deterioration. Clean screens in the venting air intake system as required. Have the entire system, including the venting system, periodically inspected by a qualified service agency.

Air Flow

Check frequently to be sure the flow of combustion and ventilation air to the unit is not obstructed.

Combustion Air Fans

Both the 399,999 - 750,000 Btu/hr models and the 990,000 - 2,070,000 Btu/hr models use a fan-assisted combustion process. The 399,999 - 750,000 Btu/hr models have one fan and the 990,000 - 2,070,000 Btu/hr models use two fans to supply combustion air to the burners.

Fan Cleaning

Check each combustion air fan every six months. Clean fan as required when installed in a dusty or dirty location. Oiling is not required.

Combustion Air Fan Adjustment

The combustion air fans are factory pre-set and should not need adjustment in most cases. Follow the steps below to adjust the fan if a continuous Low Air status code occurs.

Note: On the 399,999 - 750,000 Btu/hr models the air shutter is adjusted on the side of the fan duct as depicted in FIG. 56. On the 990,000 - 2,070,000 Btu/hr models the air shutter is adjusted on the rear of the fan duct as depicted in FIG. 58.

1.Check for proper installation and draft in venting system. Correct as required.

2.The following pressure settings are for installations up to 2000 feet altitude. Contact the factory for high altitude air pressure settings.

57

Page 57
Image 57
Lochinvar 999 - 750 Heat Exchanger Cleaning, Electrical, Combustion and Ventilation Air, Combustion Air Filter, Air Flow