Lochinvar CF-CH(E)-i&s-08 TROUBLESHOOTING GUIDE 399,999 - 750,000 Btu/hr Models, Step

Models: 399 CF-CH(E)-i&s-08 999 - 750

1 72
Download 72 pages 15.81 Kb
Page 62
Image 62

Hydronic Heating Boilers and Domestic Water Heaters

TROUBLESHOOTING GUIDE

399,999 - 750,000 Btu/hr Models

Step 1

Does the power switch

NO

Check the switch for proper

operation. Check the line voltage.

provide power to the unit?

 

 

 

Step 2

YES

 

 

 

 

 

 

Is there 24VAC at B2

NO

Combustion

NO

on the terminal strip?

 

air blower

 

 

 

 

comes on.

 

 

Check the flow switch

 

 

 

 

 

 

Tekmar pins #15 and

 

 

YES

for 24VAC.

 

 

Check all safety limit

 

devices, all connectors

 

behind the control panel

 

and voltage from the

 

transformer to B2.

and

Exchange ignition

#16

module.

Step 3

YES

NO

Check 24VAC at TH (orange wire) on the ignition module.

YES

 

 

Check staging

 

NO

relay (S2). Is

 

 

 

there 120VAC on

Does F2 on ignition module

 

the red wire to the

YES

fan?

 

have 120VAC?

 

 

 

 

 

 

YES

NO

Prepurge light comes on.

NO

Check air pressure

 

Status light does not

switch 24VAC on tan

 

 

 

blink 1 flash continuous.

 

wire (N.O.).

 

 

 

 

 

YES

NO

 

 

 

 

 

 

YES

 

 

 

 

 

 

24VAC at PS (tan wire) at ignition

Check air pressure

 

switch for correct

 

module and/or connector plug for

 

pressures.

 

proving relay secure.

 

Step 4

 

 

 

 

 

 

 

 

Trial for ignition completes

 

 

 

 

Is air switch

 

Check amp draw

YES

bouncing?

and gas valve(s) opens. Does

NO

for 3.1 amps.

 

 

not go into flame failure.

 

 

 

 

 

 

 

 

 

Replace fan.

Replace

 

 

 

 

relay.

 

Replace air pressure

 

YES

switch.

 

NO

Correct air settings.

 

 

 

 

May have to clean

 

 

burners/heat

 

YES

exchanger.

 

NO

Step 5

YES

Replace igniter if less than 2.75 amps.

Unit is running.

NO

Gas valve(s) stays open

YES

Is the flame sense signal to the

and is getting 24VAC.

 

 

 

ignition module 5uA dc or greater?

 

 

 

 

NO

Is 24VAC present at main unit connector (3x3 amp plug) red wire?

NO

Check ignition module pin #05 (replace RLY2402 if no voltage).

NO

YES

Replace gas valve.

 

Check inlet gas pressure both static and dynamic. Check manifold pressure. Check draft. Check air pressure.

62

Page 62
Image 62
Lochinvar TROUBLESHOOTING GUIDE 399,999 - 750,000 Btu/hr Models, Hydronic Heating Boilers and Domestic Water Heaters