Lochinvar 999 - 750, 399 TROUBLESHOOTING GUIDE 990,000 - 2,070,000 Btu/hr Models, Step

Models: 399 CF-CH(E)-i&s-08 999 - 750

1 72
Download 72 pages 15.81 Kb
Page 63
Image 63

Installation and

Service Manual

TROUBLESHOOTING GUIDE

990,000 - 2,070,000 Btu/hr Models

 

Does the power

Step 1

switch provide

power to the

 

 

control panel?

 

YES

Step 2

 

 

Combustion air

 

blowers come on.

 

YES

Step 3

 

 

Status light(s) does

 

not blink 1 flash

 

continuous.

 

 

 

 

Check the switch and/or

 

 

 

 

 

 

 

the line voltage.

 

 

 

 

 

 

NO

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Exchange ignition

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Check all safety limit

module.

 

 

 

Is there 24VAC at B2 on

 

NO

 

 

 

 

 

devices and voltage from

 

 

 

 

the terminal strip.

 

 

 

 

 

 

 

 

 

 

 

 

 

the transformer to B2.

 

 

NO

 

 

 

 

 

Check fan relay

 

 

 

 

 

 

 

 

 

 

NO

 

 

 

 

 

 

 

 

board. Is there

 

 

 

YES

 

 

Does F2 on ignition module

120VAC on red

 

 

 

 

 

 

 

 

 

 

 

 

YES

have 120VAC?

wires, pins #7 &

 

 

 

 

 

 

YES

#9?

 

 

 

 

 

 

 

 

 

 

 

 

Check 24VAC at TH

 

 

Check flow switch, all connectors

 

 

 

 

(orange wire) on ignition

 

 

 

 

 

 

NO

behind control panel and Tekmar

 

 

 

 

module(s).

YES

NO

 

 

 

 

output pins #16 and/or #20.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Is there continuity from the fan

Replace fan

 

 

 

 

 

 

 

relay board to fan(s)?

 

NO

 

 

Check air pressure

 

 

 

 

relay board.

 

 

switch 24VAC on tan

 

 

 

 

 

 

 

 

wire (N.O.)

 

 

 

YES

 

 

 

 

 

 

 

 

 

 

 

YES

NO

YES

Replace fan.

Replace air pressure switch.

Step 4

Does igniter(s) proof?

YES

 

24VAC at PS (tan wire) at ignition module

 

and/or connector plug for proving relay secure.

 

Check Amp draw for 3.1 amps or

NO

greater.

 

YES

 

NO

Check air pressure

YES

switch for correct

 

pressures.

NO

 

Is Air Switch

 

bouncing?

YES

 

Correct air settings may have to clean burners/heat exchanger.

Replace igniter if less than 2.75 amps.

 

 

Do the gas valve(s)

NO

 

 

open and getting

 

 

 

 

 

24VAC?

 

Step 5

 

 

 

Is the flame sense

NO

YES

 

 

 

 

signal to the ignition

 

 

 

module 5uA dc or

 

Check inlet/manifold gas pressure

greater?

 

 

both static and dynamic. Check

 

 

 

 

down draft.

 

YES

 

 

 

Step 6

 

 

 

Unit is running.

 

 

 

 

NO

 

 

 

Call our Technical

 

 

 

Service Department

 

 

 

1-800-722-2101

 

Is 24VAC present at the main unit connector

(3x5 amp plug) red and/or red - black wire,

block position #01 and #02?

 

 

 

 

 

 

 

YES

NO

 

 

 

 

 

 

 

Replace gas valve.

 

 

 

 

 

 

Check voltage at fan relay

 

board. No Voltage at pins #10

 

(red) and/or #02 (red-orange)

 

check ignition module pin #05

 

(replace RLY2402 if no

 

voltage).

No Voltage at pins

 

#08 (red-black) and/or #03

 

(red-white) check Tekmar

 

controller pins #17-18 (red-

 

black) and/or #21-22 (red-

 

white) input/output voltage.

63

Page 63
Image 63
Lochinvar 999 - 750, 399 TROUBLESHOOTING GUIDE 990,000 - 2,070,000 Btu/hr Models, Installation and Service Manual, Step