Manuals
/
Lochinvar
/
Household Appliance
/
Water System
Lochinvar
INS7162, MP2, INS7141 Typical Dwh Priority Heating Package System, Tekmar 150 Controller
Models:
TST2313
INS7162
INS7141
MP2
1
34
36
36
Download
36 pages
38.88 Kb
29
30
31
32
33
34
35
36
<
>
Install
Error codes
Boiler Reset Stand Alone
Fire Delay
External Input Signal Offset
Dip Switch Settings
temperature in the building
Testing The Control
Safety
V ac Power
Page 34
Image 34
TYPICAL DWH PRIORITY HEATING PACKAGE SYSTEM
MP2
Tekmar 150 Controller
34
Page 33
Page 35
Page 34
Image 34
Page 33
Page 35
Contents
ADDITIONAL FUNCTIONS INCLUDE
INTRODUCTION
INSTALLATION INSTRUCTIONS
USER INTERFACE
TABLE OF CONTENTS
ADJUST
MENU
External Input Signal Offset
SYMBOL DESCRIPTION
DISPLAY
Boiler Demand DHW / Setpoint Demand WWSD
SEQUENCE OF OPERATION
Boiler Reset Stand Alone
DEFINITIONS
SECTION A GENERAL OPERATION
Combustion Air C. A
Alarm
Boiler Alarm
Fixed Lead Rotation
SECTION B STAGING OPERATION
Resetting the Rotation Sequence
Resetting the Running Times
Mode
Lo / Lo
Fire Delay
Lo / Hi
Fire Delay
Auto Differential
SECTION C PUMP OPERATION
Fixed Differential
Primary Pump Purge
Boiler Pump Purge
SECTION D BOILER RESET OPERATION
FIG.
temperature in the building
This type of a hydronic radiant floor is embedded in either a thick concrete or gypsumpour. This heating system has a large thermal mass and is slow acting FIG
DHW DEMAND
SECTION E DOMESTIC HOT WATER OPERA- TION
DHW MODE OFF - NO DHW
When a DHW Demand is present, the Relay 9 / DHW con- tact terminals 30 and 31 is closed and the primary pump contact is closed. Priority can only be obtained using exter- nal wiring. During a priority override, the Relay 9 / DHW contact is opened until the heating system has recovered before returning to DHW operation, see Figure 19. This mode can be used if a DHW tank is piped in direct return and a DHW valve is installed
SECTION F SET POINT OPERATION
SETP MODE 2 - Set Point in Parallel with Priority
SECTION G EXTERNAL INPUT OPERATION
SETP MODE 1 - Setpoint in Parallel
SETP MODE 3 - Primary Pump during Set Point
0 - 10 V dc or 0 - 20 mA
2 - 10 V dc or 4 - 20 mA
General
INSTALLATION
115 V ac Power
Boiler Demand
External Input 0 - 10 V dc
Combustion Air / Alarm Contact C.A./Alarm
Set Point Demand
Primary Pump Contact Prim P1
Boiler Return Sensor
UnOccupied Switch
Relay 9 / DHW
Outdoor Sensor
DHW Demand
External Input
Boiler Demand
Set Point Demand
Relay 9 / DHW
Combustion Air or Alarm C.A. / Alarm
Primary Pump Prim P1
Relay 1 to Relay
CLEANING THE CONTROL
DIP SWITCH SETTINGS
GENERAL
Page
Page
Page
This item is only available if the External Input / Stand Alone DIP switch is set to Stand Alone
Boiler Maximum
Stage Delay
Boiler Minimum
Boil Mass
m weather
TESTING THE CONTROL
ERROR MESSAGES
TECHNICAL DATA
is not a safety limit control
TYPICAL BOILER INSTALLATION
TYPICAL BOILER INSTALLATION CONTINUED
TYPICAL DWH PRIORITY HEATING PACKAGE SYSTEM
Tekmar 150 Controller