Lochinvar TNR-I&S-02 service manual Venting, Direct Vent Installation

Models: TNR-I&S-02

1 20
Download 20 pages 57.62 Kb
Page 6
Image 6
VENTING

TNR-I&S-02

 

Figure 9

Typical Plumbing Schematic for Zoned Heating

TuboCharger Water Heater

 

VENTING

CAUTION

 

 

 

 

 

The vent shall terminate a minimum of 12 inches above expected

 

 

WARNING

 

 

 

 

snowfall level to prevent blockage of vent termination.

 

 

The vent system must be properly installed. Failure to properly install

 

The horizontal centerline of the exhaust vent terminal (if applicable)

the vent system could result in property damage, personal injury, or

 

must not be located lower than the horizontal centerline of the air

death.

 

intake terminal if vented through the same wall.

DO NOT install damaged venting system components. If damage is

 

A service drain loop must be installed in the drain tubing to serve as

 

a condensate trap to prevent flue gases from escaping in the room.

evident then please contact the supplier where the water heater was

 

DO NOT position air intake terminal above exhaust terminal.

purchased or the manufacturer listed on the rating plate for

 

NEVER locate air intake terminal when exhaust gases can be introduced.

replacement parts.

 

 

 

 

 

 

 

 

Use only the vent terminals provided or factory authorized terminals

 

NOTICE

for venting this water heater.

 

Before beginning installation of any vent pipe, read the vent pipe

 

 

 

 

manufacturer’s installation instructions.

The water heater requires its own separate venting system. Do not

 

Water heater must be protected from freezing downdrafts during

connect the exhaust vent into an existing vent pipe or chimney.

 

shutdown periods.

 

 

 

 

Provide protection of the building materials from degradation by flue

All of the exhaust venting connections must be leak checked with a

 

gases from the exhaust vent terminal.

soap solution upon initial start up of the water heater. Any leaks must

 

 

 

be repaired before continuing operation of the water heater.

 

The venting instructions must be followed to avoid restricted combustion

 

 

 

 

Do not terminate the venting where noise from the exhaust or intake

 

or recirculation of flue gases. Such conditions cause sooting or risks of fire

 

and asphyxiation.

will be objectionable. This includes locations close to or across from

 

 

 

windows and doors. Avoid anchoring the vent and intake pipes directly

 

This water heater can be installed as either a direct vent system or power

to framed walls, floors, or ceilings unless rubber isolation pipe hangers

 

 

vent (air from inside) system. If it is installed as a direct vent system,

are used. This prevents any vibrations from being transmitted into the

 

 

then the air intake and the exhaust vent are piped to the outside. If a

living spaces.

 

 

power vented system is used, then air is drawn from inside and only the

 

 

 

 

Do not exceed the venting distances or the number of elbows listed in

 

exhaust is piped to the outside. Determine which system is best for your

 

application and install as described in the following sections.

this manual. Exceeding the maximum venting distances may cause

 

 

 

the water heater to malfunction or cause an unsafe condition.

 

DIRECT VENT INSTALLATION

 

 

 

 

DO NOT operate this water heater until the venting installation is

 

Venting may be run horizontally through an outside wall or vertically

 

through a roof through using either 3 inch (7.6 cm) or 4 inch (10.2 cm)

complete and the piping completed. Failure to complete installation

 

 

diameter PVC or CPVC pipe. This water heater is supplied with a 3 inch PVC

before operation can result in property damage, personal injury, or

 

 

screened intake and exhaust 90° elbow referred to as the exhaust vent

death.

 

 

terminal and the air intake terminal.

6

Page 6
Image 6
Lochinvar TNR-I&S-02 service manual Venting, Direct Vent Installation