Insert Size Requirements (see Illustration below)

18 Insert Installation (for qualified installers only)

Insert Size Requirements (see Illustration below)

j

i

Mantel

(combustible

 

 

 

Minimum Fireplace Size

 

or

non-

 

a

Height (front)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

combustible)

b

Height (rear)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

c

Width (front)

 

Non-

 

h

 

d

Width (rear)

 

 

 

e

Depth

 

Combustible

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Facing

 

f

Hearth Depth*

 

b

 

 

 

 

 

g

Hearth Width

 

a

 

 

 

 

d

 

h

Facing Width

 

 

 

 

 

 

 

 

 

 

 

 

i

Facing Height

 

 

 

 

 

 

 

 

j

Mantel Height

Masonry

Z.C. (Metal)

Fireplace

Fireplace

20-3/4"

20-3/4"

20-3/4"

20-3/4"

23-5/8"

25-5/8"

23-5/8"

25-5/8"

13-1/2"

14-1/2"

19"

19"

39-5/8"

39-5/8"

42-5/8"

47-5/8"

32"

32"

35-1/2"

44"

Non-

c

e

 

 

 

 

 

Combustible

 

 

* This is the distance the insert protrudes from

g

 

Hearth

 

the fireplace opening plus the required 16" of

 

 

 

 

 

 

 

 

 

 

f

hearth extension.

Insert Placement Requirements

The insert must be placed so that no combustibles are within, or can swing within (e.g. drapes, doors), 36" of the front of the insert

Insert and hearth must be installed on a level, secure floor

The minimum clearances, facing, and hearth requirements in the illustration below must be met (follow the clearances for the type of fireplace being used - either masonry or zero-clearance).

 

Combustible

or

Non-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Combustible

Mantel

 

n

Combustible

Side

Top

 

Wall

 

 

 

Facing

 

 

 

 

 

 

 

 

 

 

 

 

m

 

 

k

l

p

 

Non-

 

 

 

Combustible

 

 

q

Hearth

o

x

 

 

 

 

 

Facing

Minimum Clearances

Masonry

ZC (Metal)

 

 

Fireplace

Fireplace

k

Sidewall to Insert

13"

30"

l

Side Facing

9-1/2"

12"

m

Top Facing

12"

12"

n

Mantel to Insert

15-1/2"

24"

o

Hearth (Front)*

16"

16"

p

Hearth (Side)

8"

8"

q

Front of Insert

36"

36"

x

Extension onto Hearth

3"

3"

*Does not include the distance the insert extends onto the hearth (dimension "x").

Hearth Requirements

Must extend 16" in front of the insert and 8" on both sides (total of 19" deep by 39 5/8" wide)

Must be non-combustible 1/4" thick insulating board with a thermal conductivity of K=0.72

Travis Industries

93508131

4 020327

Page 18
Image 18
Lopi Answer Wood Stove Insert Size Requirements see Illustration below, Insert Placement Requirements, Hearth Requirements