Lopi Liberty Wood Stove Floor Protection Requirements, Stove Placement Requirements, Clearances

Models: Liberty Wood Stove

1 38
Download 38 pages 28.19 Kb
Page 8
Image 8
Floor Protection Requirements

8

Stove Installation (for qualified installers only)

Floor Protection Requirements

Stove must be placed on the Travis Industries legs or Pedestal.

Floor protection must extend 6" to the sides and rear of the stove and 16" to the front of the stove (42" wide by 43" deep - see Figure 2 and Figure 3).

Floor protection must be non-combustible and at least .018" thick (26 guage).

Stove Placement Requirements

Clearances may be reduced by methods specified in NFPA 211, listed wall shields, pipe shields, or other means approved by local building or fire officials.

Stove must be placed so that no combustibles are within, or can swing within (e.g. drapes, doors), 36" of the front of the stove

If the stove is placed in a location where the ceiling height is less than 7', it must follow the requirements in the section "Alcove Installation Requirements"

Must maintain the clearances to combustibles listed below (drywall, furniture, etc.):

Clearances

The following clearances must be met (see Figure 2 and Figure 3)

 

 

 

 

 

 

Minimum Clearance

Singlewall

Reduced

 

 

 

Connector
Clearance*

 

 

 

 

 

 

A

Sidewall to stove

16"

16"

 

B

Backwall to stove

15”

10"

 

C

Cornerwall to stove

9-1/2"

7-1/2"

 

D

Connector to sidewall

28"

27-1/2"

 

E

Connector to backwall

18-1/4"

12-3/4"

 

F

Connector to cornerwall

21"

18-1/2"

 

 

 

 

 

*Reduced clearance installations require one of the chimneys and connectors listed below:

AMERI-TEC model DCC with model HS chimney

DURAVENT model DVL with DURATEC or DURA-PLUS chimney

METALFAB model DW connector with TG chimney

SECURITY model DP connector with SECURITY model ASHT or S2100 chimney

Standard Masonry Chimney with any one of the above listed connectors

NOTE: Reduced clearance connectors may not connect to the flue collar – an appliance adapter may be required.

NOTE: Standard residential installations with reduced clearance connector may use the clearance determined by the manufacturer of the connector for the connector to wall clearance or the clearance listed in this manual. Offsets must be used to maintain the stove to wall clearance.