Chimney Requirements

10

Stove Installation (for qualified installers only)

Chimney Requirements

DO NOT CONNECT THIS UNIT TO A CHIMNEY FLUE SERVING ANOTHER APPLIANCE.

Chimney connector must be a minimum 24 MSG black or 26 MSG blued steel (6" diameter). Chimney must be used from the first floor or wall penetration to the chimney cap.

Use 6" diameter type UL 103 HT chimney from one manufacturer (do not mix brands) or code approved masonry chimney with a flue liner.

Chimney connector and chimney must be fastened to the stove and each adjoining section.

Follow the chimney manufacturer's clearances and requirements.

Use the chimney manufacturer's fire stops, attic guards, roof supports, and flashings when passing through a ceiling or thimble when passing through a combustible wall.

No more than 180o of elbows (two 90o elbows, or two 45o & one 90o elbow, etc.).

NOTE: Additional elbows may be allowed if draft is sufficient. Whenever elbows are used the draft is adversely affected. Additional chimney height may be required to boost draft

Chimney Cap

 

(See the section "Chimney Termination

 

Requirements" for more details)

 

Factory Built Chimney Sections

}

Floor Penetration Equipment

 

(Attic Radiation Shield with Chimney Support)

 

}

 

Reduced Clearance Chimney

 

Connector Sections

 

Floor

 

Protection

 

Minimum System 15'

Maximum System

Roof Penetration Equipment (Roof

Radiation Shield, Flashing, Storm Collar)

Minimum Air Space to Combustibles (See Chimney Manufacturer's Instructions - usually 2")

Standard residential installations with reduced clearance connector may use the clearance determined by the manufacturer of the connector for the connector to wall clearance or the clearance listed in this manual.

Mobile home installations must use the the reduced clearance connector clearances listed in this manual under “Additional Requirements for Mobile Home Installations”.

Stove Clearance

(as outlined in this manual)

 

Figure 4

Drafting

This appliance relies upon natural draft to operate. External forces, such as wind,

Performance

barometric pressure, topography, or factors of the home (negative pressure from exhaust

 

fans, chimneys, air infiltration, etc.), may adversely affect draft. Travis Industries can not be

 

responsible for external forces leading to less than optimal performance.

 

 

Standard residential installations may use single-wall connector (Mobile-Homes may not)

Standard residential installations with reduced clearance connector may use the clearance determined by the manufacturer of the connector for the connector to wall clearance or the clearance listed in this manual. Offsets must be used to maintain the stove to wall clearance. Mobile homes must use the clearances listed in this manual under "Additional Requirements for Mobile Home Installations".