Electronic Gas Control Valve
This appliance may be fitted with a Honeywell ignition module.
Installation of the remote ON/OFF starter switch on electronic ignition units (Fig. 12):
1.Thread the wiring through the holes on the side panels of the appliance. Take care not to cut the wire or insulation on metal edges. Route the wire to a conveniently located receptacle box.
2.Attach the wire to the ON/OFF switch and install the switch into the receptacle box.
3.Connect the white wire from the wall switch to the black wire from the transformer, using an approved wire nut. Connect the black wire from the wall switch to the black wire running from the #6 position of the ignition module, also using an approved wire nut.
360DVS Series Direct Vent Fireplaces
|
| PILOT |
|
|
|
| |
|
|
| HONEYWELL IGNITION MODULE |
| |||
| MV | MV/VP | PV | 24V | 24V | SENSE SPARK | |
| GRD | ||||||
| 1 | 2 | 3 | 5 | 6 | 8 | 9 |
| RED |
|
| GREEN |
|
| BLACK |
|
|
|
|
|
| ||
|
|
|
|
|
|
| |
| ORANGE | ORANGE |
|
|
|
| |
|
|
|
|
|
|
| |
|
|
| HI |
|
|
|
|
|
|
| NOVA SIT 822 VALVE |
|
| BLUE | |
| WHITE |
|
|
|
|
| |
| POWER CORD |
|
|
|
|
|
|
| W/FEMALE SPADE |
|
|
|
|
|
|
| 120 VAC RTN | 24 VAC HOT |
|
|
| BLACK | |
|
|
|
|
|
|
| |
| WHITE |
| BLACK |
|
|
| OFF |
|
|
|
|
|
|
| WHITE |
| BLACK |
| YELLOW |
|
|
|
|
| GREEN |
|
|
|
|
|
|
| 120 VAC HOT | 24 VAC RET |
|
|
|
| |
| 40VA TRANSFORMER |
|
|
|
| WALL SWITCH | |
|
|
| BLACK | WHITE | |||
|
|
|
|
| |||
|
|
|
|
|
|
| FP1225 |
Fig. 12 | Honeywell ignition module. |
|
|
|
General Venting
Your fireplace is approved to be vented either through the side wall, or vertically through the roof.
•Only CFM Corporation venting components, specifi- cally approved and labeled for this fireplace, may be used.
•Venting terminals shall not be recessed into a wall or siding.
•Horizontal venting must be installed on a level plane without an inclining or declining slope.
There must not be any obstruction such as bushes,
garden shed, fencing, deck or utility building within 24” (610mm) from the front of the termination hood.
Do not locate the termination hood where excessive snow or ice buildup may occur. Be sure to check the vent termination area after snow falls; clear it to prevent accidental blockage of the venting system. When using a snow blower, make sure snow is not directed toward the vent termination area.
Location of Vent Termination
It is imperative the vent termination be located observ- ing minimum clearances as shown on the following page.
10006326 | 13 |