Majestic Appliances 360DVS3 Troubleshooting the Gas Control System, Symptom, Possible Causes

Models: 360DVS3 360DVS2 360DVSR 360DVSL

1 44
Download 44 pages 34.52 Kb
Page 30
Image 30
Troubleshooting the Gas Control System

360 DVS Series Direct Vent Fireplaces

Troubleshooting the Gas Control System

SIT NOVA 820 MILLIVOLT VALVE

NOTE: Before troubleshooting the gas control system, be sure external gas shut off is in the “On” position.

WARNING: REMOVE GLASS FRONT BEFORE DOING ANY GAS CONTROL SERVICE WORK.

SYMPTOM

POSSIBLE CAUSES

CORRECTIVE ACTION

 

 

 

1. Spark ignitor will not light

A. Defective or misaligned

Using a match, light pilot. If pilot lights, turn off

 

electrode at pilot.

pilot and push the red button again. If pilot will not

 

 

light, check the gap at electrode and pilot; it should

 

 

be 1/8” to have a strong spark.

 

B. Defective ignitor (Push Button)

Push piezo Ignitor Button. Check for spark at

 

 

electrode and pilot. If no spark to pilot, and electode

 

 

wire is properly connected, replace ignitor.

2. Pilot will not stay lit after

A. Defective pilot generator

Check pilot flame. Must impinge on thermocouple/

carefully following lighting

(thermocouple), remote wall

thermopile. NOTE: This pilot burner assembly

instructions.

switch.

utilizes both a thermocouple and a thermopile.

 

 

The thermocouple operates the main valve opera-

 

 

tion (ON/OFF). Clean and/or adjust pilot for maxi-

 

 

mum flame impingement on thermopile and thermo-

 

 

couple.

 

B. Defective automatic valve

Turn valve knob to “Pilot.” Maintain flow to pilot;

 

 

millivolt meter should read greater than 10 mV. If

 

 

the reading is okay and the pilot does not stay on,

 

 

replace the gas valve. NOTE: An interrupter block

 

 

(not supplied) must be used to conduct this test.

3. Pilot burning, no gas to

A. Wall switch or wires defective

Check wall switch and wires for proper connections

main burner

 

Jumper wires across terminals at wall switch; if

 

 

burner comes on, repalce defective wall switch. If

 

 

okay, jumper wires across wall switch wires at valve;

 

 

if burner comes on, wires are faulty or connections

 

 

are bad.

 

B. Thermopile may not be

1. Be sure wire connections from thermopile at

 

generating sufficient

gas valve terminals are tight and thermopile is

 

millivoltage.

fully inserted into pilot bracket.

 

 

2. One of the wall switch wires may be grounded.

 

 

Remove wall switch wires from valve terminals if

 

 

pilot now stays lit, trace wall switch wiring for

 

 

ground. May be grounded to fireplace or gas

 

 

supply.

 

 

3. Check thermopile with millivolt meter. Take

 

 

reading at thermopile terminals of gas valve—

 

 

should read 250-300 millivolts (minimum 150)

 

 

while holding valve knob depressed in pilot

 

 

position and wall switch “OFF.” Replace faulty

 

 

thermopile if reading is below specified minimum.

 

C. Plugged burner orifice.

Check burner orifices for debris and remove.

 

D. Defective automatic valve

Turn valve knob to “ON,” place wall switch to “ON” —

 

operator.

millivolt meter should read greater than 100 mV. If

 

 

the reading is okay and the burner does not come

 

 

on, replace the gas valve.

4. Frequent pilot outage

A. Pilot flame may be too low

Clean and/or adjust pilot flame for maximum flame

problem.

or blowing (high) causing the

impingement on thermopile and thermocouple.

 

pilot safety to drop out.

 

 

B. Possible blockage of the vent

Check the vent terminal for blockage (recycling the

 

terminal.

flue gases)

30

10006326

Page 30
Image 30
Majestic Appliances 360DVS3 Troubleshooting the Gas Control System, DVS Series Direct Vent Fireplaces, Symptom, 10006326