Power Supply Cord
Fire Hazard
Use a new UL listed 30 amp power supply cord.
Use a UL listed strain relief.
Disconnect power before making electrical connections.
Connect neutral wire (white or center wire) to center terminal (silver).
Ground wire (green or bare wire) must be connected to green ground connector.
Connect remaining 2 supply wires to remaining 2 terminals (gold).
Securely tighten all electrical connections.
Failure to do so can result in death, fire, or electrical shock.
1. Disconnect power.
2.Remove the
A. Neutral ground wire
D B. Externalground conductor screw C. Centel,
block screw
D. Terminalblock cover and hoM-
down screw
Direct Wire
Fire Hazard
Use 10 gauge solid copper wire.
Use a UL listed strain relief.
Disconnect power before making electrical connections.
Connect | neutral wire (white or center wire) to center | Z |
terminal | (silver). |
|
Ground wire (green or bare wire) must be connected to green ground connector.
Connect remaining 2 supply wires to remaining 2 terminals (gold).
Securely tighten all electrical connections.
Failure to do so can result in death, fire, or electrical shock.
3.Install strain relief.
Style 1 : Power supply cord strain relief
•Remove the screws from a s/4" (1.9 cm) UI_ listed strain relief (UI_ marking on strain relief). Put the tabs of the two clamp sections into the hole below the terminal block opening so that one tab is pointing up and the other is pointing down, and hold in place. Tighten strain relief screws enough to hold the two clamp sections together.
s_ _ _
A. Strain refief tab pointing up
B. Hole below terminal block opening
C. Clamp section
D. Strain refief tab pointing down