Mercury PR0091 Connections, Do not connect an earth, Input/Output Allocation Tables, Alarm Action

Models: PR0091

1 21
Download 21 pages 19.6 Kb
Page 4
Image 4
Connections

Mercury 6-5 Stat – Installation & User Guide

Connections

All connections are made to the back of the controller. The diagram below shows the connection detail. Inputs and outputs are assigned according to the chosen configuration. See Specification for further details on connections.

!Do not connect an earth.

Input/Output Allocation Tables

An over-ride can be achieved by switching in a fixed value resistor in parallel with the probe inputs as shown in the table below.

 

5 Ch Thermostat

Description

 

Alarm Action

(Switched Resistor)*

 

 

 

 

 

 

 

Input 1

Probe 1 and Over-ride 1

 

Yes

Over-ride signal 1

 

Input 2

Probe 2 and Over-ride 2

 

Yes

Over-ride signal 2

 

Input 3

Probe 3 and Over-ride 3

 

Yes

Over-ride signal 3

 

Input 4

Probe 4 and Over-ride 4

 

Yes

Over-ride signal 4

 

Input 5

Probe 5 and Over-ride 5

 

Yes

Over-ride signal 5

 

Relay 1

Thermostat Channel 1

 

N/A

 

 

Relay 2

Thermostat Channel 2

 

N/A

 

 

Relay 3

Thermostat Channel 3

 

N/A

 

 

Relay 4

Thermostat Channel 4

 

N/A

 

 

Relay 5

Thermostat Channel 5

 

N/A

 

* For PT1000 probes use 820 Ohm

 

 

 

For NTC2000 and NTC2k25 probes use 590 Ohm

 

 

Ensure that all power is

 

 

 

 

switched off before

 

 

 

 

installing or maintaining

 

 

 

 

this product

Revision 1.2

Page 4 of 21

Page 4
Image 4
Mercury PR0091 manual Connections, Do not connect an earth, Input/Output Allocation Tables, Ch Thermostat, Alarm Action