Mercury PR0091 manual Specification, General, Power requirements, Relays

Models: PR0091

1 21
Download 21 pages 19.6 Kb
Page 16
Image 16
Specification

Mercury 6-5 Stat – Installation & User Guide

Specification

 

General

 

Power requirements:

 

Supply Voltage Range:

100 - 240 Vac ±10%

Supply Frequency:

50 - 60 Hz ±10%

Maximum supply current:

<1 Amp (With no relay loads)

Typical supply current:

<0.5 Amp

Operating temperature range:

+50C to +500C

Operating Humidity:

80% maximum

Storage temperature range:

-200C to +650C

Environmental:

Indoor use at altitudes up to 2000m, Pollution Degree 1,

 

Installation Category II.

 

Voltage fluctuations not to exceed ±10% of nominal voltage

Size:

110mm (W) x 60mm (H) x 100mm (D)

Weight:

150 Grams

Safety:

EN61010

EMC:

EN61326; 1997 +Amdt. A1; 1998

Ventilation:

There is no requirement for forced cooling ventilation

Class 2 Insulation:

No protective Earth is required and none should be fitted.

The host equipment must provide a suitable external over-current protection device such as: -

Fuse:

6.3A 240 Vac Antisurge (T) HRC conforming to IEC 60127

Or MCB:

8A, 240 VAC Type C conforming to BS EN 60898

The host equipment must provide adequate protection against contact to hazardous live parts.

Relays

 

 

Max current relay 1:

6A (non inductive)

 

Max Voltage relay 1:

260Vac (external supply)

 

Exclusive common

 

 

Max current relay 2:

4A (non inductive)

Relays 2 and 3 share a common

Max Voltage relay 2:

260Vac (external supply)

supply line and the loads can

Shared common with relay 3

 

have a combined total of 8A.

 

 

Relay 2 or 3 can switch a maximum

Max current relay 3:

4A (non inductive)

of 6A provided the other is at 2A or.

Max Voltage relay 3:

260Vac (external supply)

lower.

Shared common with relay 2

 

 

Max current relay 4:

3A (non inductive)

 

Max Voltage relay 4:

260Vac (Internal supply)

 

Common connected to Input "live"

 

 

Max current relay 5:

3A (non inductive)

 

Max Voltage relay 5:

260Vac (Internal supply)

 

Common connected to Input "live"

 

 

For compliance with the LVD, relays 2 and 3 common must be at the same potential as the supply voltage.

!

Warning:

 

 

Relays 4 and 5 outputs have hazardous voltages (Supply input voltage potential).

 

 

Ensure that all power is

 

 

 

switched off before

 

 

 

installing or maintaining

 

 

 

this product

Revision 1.2

Page 16 of 21

Page 16
Image 16
Mercury PR0091 manual Specification, General, Power requirements, Relays