Mercury
Parameter table for 5 Channel Thermostat Continued.......
Number | Parameter | Range | Step | Units | Default |
P79 | Tuesday On Time 1 | 00:00 to 23:59 | 00:01 | hh:mm | 08:00 |
P80 | Tuesday Off Time 1 | 00:00 to 23:59 | 00:01 | hh:mm | 20:00 |
P81 | Tuesday On Time 2 | 00:00 to 23:59 | 00:01 | hh:mm | 08:00 |
P82 | Tuesday Off Time 2 | 00:00 to 23:59 | 00:01 | hh:mm | 20:00 |
P83 | Wednesday On Time 1 | 00:00 to 23:59 | 00:01 | hh:mm | 08:00 |
P84 | Wednesday Off Time 1 | 00:00 to 23:59 | 00:01 | hh:mm | 20:00 |
P85 | Wednesday On Time 2 | 00:00 to 23:59 | 00:01 | hh:mm | 08:00 |
P86 | Wednesday Off Time 2 | 00:00 to 23:59 | 00:01 | hh:mm | 20:00 |
P87 | Thursday On Time 1 | 00:00 to 23:59 | 00:01 | hh:mm | 08:00 |
P88 | Thursday Off Time 1 | 00:00 to 23:59 | 00:01 | hh:mm | 20:00 |
P89 | Thursday On Time 2 | 00:00 to 23:59 | 00:01 | hh:mm | 08:00 |
P90 | Thursday Off Time 2 | 00:00 to 23:59 | 00:01 | hh:mm | 20:00 |
P91 | Friday On Time 1 | 00:00 to 23:59 | 00:01 | hh:mm | 08:00 |
P92 | Friday Off Time 1 | 00:00 to 23:59 | 00:01 | hh:mm | 20:00 |
P93 | Friday On Time 2 | 00:00 to 23:59 | 00:01 | hh:mm | 08:00 |
P94 | Friday Off Time 2 | 00:00 to 23:59 | 00:01 | hh:mm | 20:00 |
P95 | Saturday On Time 1 | 00:00 to 23:59 | 00:01 | hh:mm | 08:00 |
P96 | Saturday Off Time 1 | 00:00 to 23:59 | 00:01 | hh:mm | 20:00 |
P97 | Saturday On Time 2 | 00:00 to 23:59 | 00:01 | hh:mm | 08:00 |
P98 | Saturday Off Time 2 | 00:00 to 23:59 | 00:01 | hh:mm | 20:00 |
dFLt | Factory Defaults |
|
|
|
|
Units and Probe Type
Change the probe type to: -
0 | = PTC1000 oC | Range |
1 | = PTC1000 oF | Range |
2 | = NTC2000 oC | Range |
3 | = NTC2000 oF | Range |
4 | = NTC2k25 oC | Range |
5 | = NTC2k25 oF | Range |
Probe Fault
If a probe fault occurs then the controller will pulse its associated relay(s) on for 5 minutes then off for 5 minutes.
Ensure that all power is |
|
|
switched off before |
|
|
installing or maintaining |
|
|
this product | Revision 1.2 | Page 9 of 21 |