MGE UPS Systems 2000, 3000 VA user manual Hot swap, Connection of equipment to a terminal block

Models: 3000 VA 2000

1 34
Download 34 pages 36.25 Kb
Page 17
Image 17

2. Installation

Hot swap

Before carrying out any connections, check that the battery circuit breaker 8 is OFF and that the electrical power cord to the AC-power source is disconnected.

Connection of equipment to outlets

Plug your equipment into the outlets 2 .

 

 

 

 

 

Connection of equipment to a terminal block:

 

 

 

 

 

This type of connection must be carried out by qualified

 

 

 

 

2

electrical personnel.

 

 

 

 

 

 

 

 

 

1.

Remove the terminal-block cover 32 .

 

 

 

 

 

2.

Insert the cable supplying the equipment through the cable

 

 

 

 

 

 

 

 

 

 

clamp 33 .

 

 

 

 

 

3.

Connect the three wires to the output terminal block 5 .

8

32

33

5 Output terminal block

Phase

Neutral

Earthing wire

1

29

Always connect the earthing wire first.

4.Remove the terminal-block cover.

5.Tighten the nut on the cable clamp 33 .

The overall cable diameter and the cross-sectional area of the three wires depends on the UPS rating.

 

Pulsar EXtreme

Pulsar EXtreme

 

2000

3000

 

 

 

Cable diameter

From 9 to 12 mm

From 9 to 12 mm

 

 

 

Cross-sectional area of each wire

1 to 4 mm2

1,5 to 4 mm2

Recommended upstream

 

 

circuit breaker

 

 

Nominal rating

C60N 10A 2P

C60N 16A 2P

(47 to 63Hz, 230V)

(maximum line

(maximum line

 

current = 9A)

current = 13A)

Maximum rating

C60N 16A 2P

C60N 20A 2P

(47 to 63Hz, 187V)

(maximum line

(maximum line

 

current = 11A)

current = 16A)

 

 

 

Connection to the AC-power source:

1.Connect the electrical power cord 29 to the socket 1 for connection to AC-power source.

2.Connect the other end of the electrical power cord

to an AC-power outlet.

51033211EN/AC - Page 17

Page 17
Image 17
MGE UPS Systems 2000 Hot swap, Connection of equipment to a terminal block, Always connect the earthing wire first