3. Operation
3.2 Start-up
Prior to initial
The frequency of the output voltage (50 or 60 Hz) is automatically set to that of the input source.
8
24
1.Close the upstream device (ON position) controlling the supply of AC power to the UPS.
2.Set the battery circuit breaker(s) 8 to ON.
The buzzer beeps three times.
If the supply frequency is different than the default value set on the UPS, the new value is set and the buzzer beeps 4 times.
3. Press the ON / OFF button 24 .
All the equipment connected to the UPS is now energised, however it takes another 30 seconds before the UPS is fully operational.
After this time, the equipment connected to the UPS is protected.
◗If LED 22 or 23 do not go ON or if one of LED 14 , 15 , 16 or 17 flash, there is a fault (see section 4.1). ◗In order to detect any wiring errors, it is essential that the
3.3Bargraph indications
LEDs 14 to 17 provide three different indications.
14 |
15 |
16 |
17 |
18 |
Page 20 - 51033211EN/AC |
1.Remaining backup time in percent.
2.Percent load drawn by the protected equipment, when button 18 is pressed.
3.Operating faults (flashing LED and beeps):
14Overload.
15UPS fault.
16Battery fault.
17Excessive ambient temperature.