20

21

22

24

8

10

31 3

31

4. Maintenance

Reconnection:

1.Insert the connection module in the connector 10 and secure using the two screws 31 .

2.Switch the battery circuit breaker(s) 8 to the ON position and check that LED 20 is ON.

Check that UPS personalization settings still correspond to the equipment to be supplied (see section 3.5).

3.Press button 24 and wait 20 seconds.

4.Check that LED 21 is ON.

If LED 21 is not ON, do not switch to the intermediate position and call the after-sales support department.

5.Turn the manual bypass switch 3 from the BYPASS position to the intermediate position and check that LED 20 is ON.

6.Turn the manual bypass switch 3 from the intermediate position to the NORMAL position. LED 21 goes OFF and LED 22 goes ON.

The connected equipment is again protected by the UPS.

51033211EN/AC - Page 29

Page 29
Image 29
MGE UPS Systems 2000, 3000 VA user manual Press button 24 and wait 20 seconds Check that LED 21 is on