3. Operation

"Battery" tab

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Personalizable function

 

 

 

Default setting

 

 

Options

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Once a week

 

"Battery test" intervals

 

 

 

Every day

 

 

Once a month

 

 

 

 

 

 

 

 

No test

 

 

 

 

 

 

 

 

 

"Low-battery shutdown warning" threshold

 

20% remaining battery

 

 

40% remaining battery

 

 

 

 

 

backup time

 

 

backup time

 

 

 

 

 

 

 

 

 

 

Charger

 

 

 

Standard

 

 

CLA (2, 4 or 8 hours)

 

 

 

 

 

 

 

 

 

"Output" tab

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Rated AC-power source voltage (see figure 1)

 

 

230 V

 

 

200 V-208 V-220 V-240 V

 

 

 

 

 

 

 

 

 

 

Rated AC-power source frequency

 

 

50 Hz

 

 

60 Hz

 

 

 

 

 

 

 

 

 

 

Tolerance for AC-power source frequency

 

± 5%

±

1% to ± 10% , in 1% steps

 

 

 

 

 

 

 

 

 

 

Overload alarm level

 

100%

 

 

0 to 100%, in 10% steps

 

 

 

 

 

 

 

 

 

UPS restart after a short-circuit

 

 

Disabled

 

Enabled (click to add check)

 

 

 

 

 

 

 

 

 

"By-pass" tab

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Authorized voltage range for transfer to bypass

 

187 V to 265 V (for

 

 

187 V to 265 V,

 

if fault or overload

 

 

230 V rated voltage)

 

 

in 1V steps

 

 

 

 

 

 

 

Authorized frequency range for transfer to bypass

 

± 10%

±

1% to ± 10%, in 1% steps

 

if fault or overload

 

 

 

 

 

 

 

 

 

 

 

 

 

Transfer to bypass if overload

 

 

Enabled

Disabled (click to remove check)

 

 

 

 

 

 

 

Transfer to bypass following a fault, whatever

 

 

Disabled

Enabled (click to add check)

 

the conditions on the AC-power source

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

The value selected for the rated UPS voltage impacts on the power available at UPS output (see the diagram below).

100%

95%

90%

66%

50%

Available power as a percentage of the rated power

84

Voltage in V

Fig. 1

51033211EN/AC - Page 23

Page 23
Image 23
MGE UPS Systems 2000, 3000 VA Battery tab, Output tab, By-pass tab, Personalizable function Default setting Options