MGE UPS Systems 800 Rack Technical characteristics, AC-input power, On battery power, Environment

Models: 500 Rack 800 Rack 1500 Rack 1100 1100 Rack 1500

1 196
Download 196 pages 60.21 Kb
Page 30
Image 30

6. Appendices

Technical characteristics

Pulsar Evolution

500

 

800 / 800 rack

 

1100 / 1100 rack

 

1500 / 1500 rack

 

 

 

 

 

 

 

 

 

Output rating

500 VA / 350 W

 

800 VA / 560 W

 

1100 VA / 700 W

 

1500 VA / 1000 W

 

 

 

 

 

 

 

 

 

AC-input power

 

 

 

 

 

 

 

 

Voltage

 

 

Single-phase, 160 V to

294 V (1) , 230V nominal.

 

 

Frequency

47 Hz to 70

Hz (50 Hz system) or

56.5 Hz to 70 Hz (2) (60

Hz system)

 

 

 

 

 

 

 

 

 

Output power (operation

 

 

 

 

 

 

 

 

on battery power)

 

 

 

 

 

 

 

 

Voltage

 

 

Single-phase, 230

 

V (3) (+ 6% / - 10%)

 

 

Frequency

 

 

50/60 Hz

 

+/- 0.1 Hz

 

 

 

 

 

 

 

 

 

 

 

Battery (sealed lead-acid,

 

 

 

 

 

 

 

 

maintenance free)

 

 

 

 

 

 

 

3 x 12 V - 9 Ah,

Tower models

 

 

2 x 12 V - 7.2 Ah,

 

2 x 12 V - 9 Ah,

 

Rack models

2 x 6 V - 9 Ah,

 

4 x 6 V - 7.2 Ah

 

4 x 6 V - 9 Ah

 

6 x 6 V - 9 Ah

 

 

 

 

 

 

 

 

 

Environment

 

 

 

 

 

 

 

 

Noise level (operation on

 

 

<40 dBA

 

 

 

 

<40 dBA

AC-input power)

 

 

 

 

 

 

 

 

Operating temperature

 

 

0 to 35° C

 

 

 

 

0 to 40° C

Relative humidity

 

 

 

 

 

 

 

 

(without condensation)

 

 

20 to 90%

 

 

 

 

20 to 90%

 

 

 

 

 

 

 

 

 

(1)The upper and lower thresholds may be set using the UPS Driver software.

(2)Or 40 Hz in low-sensitivity mode (may be set using the UPS Driver software).

(3)Adjustable from 200 to 240 V using the UPS Driver software.

34007117EN/AB - Page 29