getting started (continued)

installing the "automatic bypass" module (option)

The "automatic bypass" module plugs into the back of Pulsar EX:

cunscrew the cover protecting the connector 15 for the "automatic bypass" module;

cremove the wire linking two of the terminals of the connector (grounding the neutral when the automatic bypass module is not connected);

cplug the module 21 into the connector 15 (see figure 3);

ctighten the module using the 2 screws in the connector 15 .

Pulsar EX with the "manual bypass" module ("Hot- swap" version)

c ensure that the "automatic bypass"

module 21 is properly installed;

c take the "manual bypass" module 25 ;

c plug the rear connectors into connectors

4 and 6 of Pulsar EX (see figure 4);

c tighten the module using the 2 screws

24 ;

 

 

12

AC outlet

 

21

 

 

 

26

 

 

 

15

 

 

 

 

 

 

3

 

7

 

27

 

 

5

 

6

 

 

 

24

 

2

 

 

 

 

23

 

 

 

 

 

1

 

31

 

XB2 29 30 XB1

Figure 3

Figure 4

 

 

c plug the connecting cable 26 into the

connector 12 of Pulsar EX;

c connect the loads having to be supplied

by Pulsar EX:

v either directly in the sockets 23 of the

module,

v or, in the case of cable connection, open

the cover protecting the terminal blocks,

pass the cable in the left cable-clamp and

connect the 3 wires (phase, neutral and

ground) in the output terminal block 29

(XB2) and put back the protective cover.

cconnect Pulsar EX to the AC outlet by the power cable 5 connected to the input socket 27 of the module, having first removed the protective cover.

If you cannot use the power cable 5 included with the module, you can made this cable by yourself, by taking the female plug of cable 5 included and connecting on it the 3 wires (phase, neutral and ground) of your cable as indicated in figure opposite.

G

N

Ph

cdo not connect the power cable 5 to the AC outlet if the battery extension module option has to be installed, else directly consult the "operation" section.