reconnecting Pulsar EX
Operating mode:
c take the "manual bypass" module 25 or |
31 and connect it behind Pulsar EX; |
c screw on this module using the 2 screws |
24 ; |
c plug the cable 26 into the connector 12 |
on Pulsar EX; |
c close the battery |
Pulsar EX (as well as the |
32 on the Pulsar EXB battery extension |
modules if fitted): "l" position; |
c with the "manual bypass" switch 28 set |
cif the indicator lights are in a status other than that indicated, do not switch the "manual bypass" and contact our
cswitch the "manual bypass" 28 from the
The following indications are obtained:
… | 1a to 1d n/a |
| |
… | ! |
… | - + |
… |
|
"manual bypass" switch 28
NORMAL 

BY-PASS
NORMAL |
to |
c check after 15 seconds that Pulsar EX |
has started properly and that the following |
indications are obtained: |
%
…
-
+
1e off/power on
flashing/load in
1f "automatic bypass"
intermittent beeps
intermediate position
| … | 1a to 1c off | |
|
| ||
| … | ! |
|
| … | - + |
|
| … | 1d | flashing/operation on |
| "manual bypass" | ||
|
| ||
|
|
| |
% | … | - + 1e off/power on | |
|
1f flashing
intermittent beeps
cswitch the "manual bypass" 28 from the intermediate position to the "NORMAL" position: operation is now normal and the following indications are obtained:
| … | 1a to 1d indicate battery state | |
|
| ||
| … | ! | |
| … | - + | |
| … |
| |
| … | off/power on | |
% | - + 1e flashing/power off | ||
|
1f on/load energized
silence
NORMAL 

BY-PASS
"NORMAL" position
Figure 10