operation (continued)

return of AC power

cregardless of the point in the above sequence at which AC power is restored, Pulsar EX will switch to normal operation:

 

 

indicate the battery

 

 

1a to 1d charge level (here,

 

 

 

 

!

between 10% and 20%)

 

- +

 

 

 

 

%

- +

1e off/power on

 

1f on/load energized

1 long beep

cyour loads are being supplied by

Pulsar EX.

load level

cPulsar EX is now running. Press and hold down the test button 2 :

 

1a to 1d

indicate the load level

 

 

(here, between 90%

 

!

and 100%)

 

- +

 

 

 

 

 

off/power on

%

- + 1e flashing/power off

 

1f on/load energized

silence

cyour loads are being supplied by

Pulsar EX.

overload

coverloading occurs if the power consumption of the supplied loads exceeds the rated output of Pulsar EX.

 

1a flashing/overload

 

 

 

!

 

- +

 

 

 

off/power on

%

- + 1e flashing/power off

 

1f on/load energized

intermittent beeps

ccase of a device not fitted with the "automatic bypass" option 21 :

v Pulsar EX will shut down after a delay ranging from 100 ms to 1 minute depending on the overload level;

ccase of a device fitted with the "automatic bypass" option 21 :

v if the power is within the operating range, after a delay ranging from 100 ms to 1 minute, the load will be switched to the AC for 20s and then back to the UPS,

v if the overload persists, Pulsar EX will shut down and your loads will no longer be supplied,

v if the power is not within the operating range, Pulsar EX will shut down after a delay ranging from 100 ms to 1minute and

your loads will no longer be supplied.