disconnecting Pulsar EX

The "manual bypass" switch 28 is used to remove Pulsar EX for maintenance purposes or standard exchange, while guaranteeing continuity of power supply to your loads.

Operating mode:

cswitch the "manual bypass" 28 from the "NORMAL" position to the intermediate position (see figure 9);

ccheck that, in this position, the "automatic bypass" has been put into operation: indicator light 1f is flashing;

cif the indicator light 1f is still on, the transfer to the "automatic bypass" has not taken place (power voltage or frequency not within the operating range). In this case do not switch to the "BYPASS" and call our after-sales service.

cmove the "manual bypass" switch 28 from the intermediate to the "BY-PASS" position. The display should show:

 

1a to 1c off

 

 

 

!

 

 

- +

 

 

1d

flashing/operation on

 

"manual bypass"

 

 

 

 

 

%

- + 1e off/power on

 

1f flashing

intermittent beeps

c shut down Pulsar EX, by releasing the

"ON/OFF" button 3 ;

c open the battery circuit breaker 7 on

"manual bypass" switch 28

NORMAL BY-PASS

"NORMAL" position

NORMAL

BY-PASS

intermediate position

%

… … … …

!

-+

-+

1a to 1d n/a

1e off/power on

flashing/load in

1f "automatic bypass"

intermittent beeps

Pulsar EX, and the battery circuit breaker

32 on the Pulsar EXB battery extension

module, if it is fitted;

c disconnect the cable 26 of the connector

12 of Pulsar EX;

c unscrew the "manual bypass" module 25

or 31 (screw 24 ) and remove it from

Pulsar EX.

Your loads are supplied directly by the AC

power via the "manual bypass" module and

Pulsar EX is powered down.

You may now change the UPS, replacing it

with another UPS of the same type, without

interrupting your load. In this case do not

forget to unplug and store the "automatic

bypass" cartridge 21 .

NORMAL BY-PASS

"BY-PASS" position

Figure 9