Pulsar EX with the "manual bypass" module ("Install" version)

censure that the "automatic bypass" module 21 is properly installed;

ctake the "manual bypass" module 31 ;

cplug the rear connectors into connectors 4 and 6 of Pulsar EX (see figure 5);

ctighten the module using the 2 screws 24 ;

cplug the connecting cable 26 into the connector 12 of Pulsar EX;

cconnect the loads having to be supplied by Pulsar EX:

v open the cover protecting the terminal blocks, pass the cable in the left cable- clamp and connect the 3 wires (phase, neutral and ground) to the output terminal block 29 (XB2).

cconnect Pulsar EX to the AC supply;

vpass the cable in the right cable-clamp and connect the 3 wires (phase, neutral and ground) to the input terminal block 30 (XB1) and put back the protective cover;

c do not connect the supply cable to the AC outlet if the battery extension module option has to be installed, else directly consult the "operation" section.

12

26

24 25

7

6

AC power (single-phase + earth)

29 Ph N Ph N 30

XB2XB1output to load

Figure 5

30