operation on battery

when the AC power fails, the operating sequence is the following:

AC power failure

low-battery

automatic shutdown of

 

shutdown warning

Pulsar EX at end of

 

 

backup time

if Pulsar EX is operating with no load (power-saving mode set up using EX Driver): device will be shut down after 5 mn

0 mn

 

 

 

 

%

!

-+

-+

indicate the

1a to 1d remaining battery backup time (here, between 70% and 90%)

1e flashing/power off

80% T mn

 

1a to 1c off

 

 

 

!

 

 

 

 

 

- +

 

 

1d

flashing/low-battery

 

 

 

shutdown

 

 

warning

%

- + 1e flashing/power off

 

T mn

 

1a

to 1d off

 

 

 

!

 

 

 

 

 

- +

 

 

 

 

%

- + 1e

flashing/power off

 

5 mn

 

1a

to 1d off

 

 

 

!

 

 

 

 

 

- +

 

 

 

 

%

- + 1e

offflashing/power

1f on/load energized

1f on/load energized

1f off/load de-energized

1f off/load de-

energized

3 short beeps

cyour loads are being supplied by Pulsar EX from battery power.

intermittent beeps

silence

c there is less than 20% of

c your loads are no longer

battery backup time left:

being supplied.

shut down your applications

 

as automatic shutdown of

 

Pulsar EX is imminent.

 

silence

cyour loads are no longer

being supplied.

MGE UPS SYSTEMS

Pulsar EX : 51032306XT/BB

33

Page 43
Image 43
MGE UPS Systems EX30, EX20, EX40 Operation on battery, AC power failure Low-battery, 1a to 1c off, There is less than 20%