Table 4-2. Electrical Service Requirements*
Input Voltage | 230 | 460 |
|
|
|
Recommended Standard Fuse Or Circuit Breaker Rating In Amperes1 | 250 | 125 |
Input Conductor Size In AWG/Kcmil2 | 1/0 | 4 |
Max Input Conductor Length In Feet (Meters)3 | 229 (70) | 397 (121) |
Grounding Conductor Size In AWG/Kcmil4 | 4 | 6 |
*These values are calculated from the 1993 edition of the National Electrical Code (NEC).
1 Recommended fuse or circuit breaker size is that closest to 150% of rated input amperage of the welding power source. Article
2 Input conductor size is for insulated copper wire with 75° C rating with not more than three single
3 Maximum length is to prevent more than a 3% voltage drop between service entrance and input terminals of the welding power source (Articles
4 The grounding conductor shall be colored or identified as specified in the NEC. Grounding conductor size for copper wire is not required to be larger than input conductor (Article
SECTION 5 – MAINTENANCE & TROUBLESHOOTING
WARNING |
ELECTRIC SHOCK can kill.
• Do not touch live electrical parts.
• Turn Off welding power sources, and disconnect input power to rack before inspecting, maintaining, or servicing.
Maintenance to be performed only by qualified persons.
5-1. Routine Maintenance
3 Months
Tape Or
Replace
Cracked
Cables
| Replace |
See | Unreadable |
Section | Labels |
7 |
|
Clean
And
Tighten Weld
Connections
Turn Off all power before maintaining.
| 6 Months |
OR | Blow Out |
Or | |
| Vacuum |
| Inside |
| During Heavy Service, |
– – | Clean Monthly |