SECTION 13: TROUBLESHOOTING
SECTION 13: TROUBLESHOOTING 13.1 General
WARNING
Explosion Hazard
Installation, service and annual inspection must be done by a contractor qualified in the installation and service of
START
Are gas & electrical | No | |
supplies on? | ||
| ||
Yes |
| |
Is ignition control showing a | Yes | |
"4 flashes" LED code? |
No
Turn on supplies.
UHD 75: Press in reset
button on manual reset limit switch. UHD 100 - 125: Wait
10 - 15 minutes for limit Yes switch to cool. Does fan
stop running?
No
Replace temperature limit
switch.
Turn off gas and electrical supplies before performing service or maintenance.
Failure to follow these instructions can result in death, injury or property damage.
Fan and limit switch are operating normally.
Is ignition control showing a | Yes | Burner has locked out due | |
to ignition failure. Use | |||
"2 flashes" LED code? |
| Troubleshooting for Automatic | |
|
| ||
|
| Ignition Burner Systems | |
|
| section to test burner. | |
No |
|
| |
Does the flue blower run? | No | Use Troubleshooting for | |
Flue Blower section to test | |||
| |||
|
| fan. | |
Yess |
|
| |
With external controls (i.e. | No | Has burner “Locked Out”? No | |
thermostat) on, does the | |||
burner continue through the |
|
| |
heating cycle? |
|
| |
|
| Yes | |
|
| Use Troubleshooting for | |
|
| Automatic Ignition Burner | |
|
| Systems section to test burner. | |
Yes |
|
| |
Heater Operating |
| If problems persist, contact | |
No | |||
TROUBLESHOOT ENDS. | |||
|
The limit switch has
tripped. See Manual Reset No Replace limit switch. Limit Switch Figure.
Yes
Ensure air flow through the
heat exchanger is
appropriate per the rating
plate.
31