Attach this information to the wall near the ROBERTS GORDON® heater

®

Read the Installation, Operation and Service Manual thoroughly before installation, operation or service.

OPERATING INSTRUCTIONS

WARNING

1.STOP! Read all safety instructions on this information sheet.

2.Open the manual gas valve in the heater supply line.

3.Turn on electric power to the heater.

4.Set the thermostat to desired setting (above ambient temperature). The automatic starting sequence begins.

TO TURN OFF THE HEATER

1.Turn the thermostat/time switch to 'OFF' or lowest setting. The burner will turn 'OFF' immediately, but fans will continue to cool heat exchanger until the fan thermostat switches off.

IF THE HEATER WILL NOT OPERATE, TO ENSURE YOUR SAFETY, FOLLOW THESE INSTRUCTIONS TO SHUT DOWN YOUR HEATER

1.Set the thermostat to off or the lowest setting.

2.Turn off electric power to the heater.

3.Turn off the manual gas valve in the heater supply line.

4.Call your installer/contractor qualified in the installation and service of gas-fired heating equipment.

Fire Hazard

Some objects can catch fire or explode when placed close to heater.

Keep all flammable objects, liquids and vapors the required clearances to combustibles away from heater.

Failure to follow these instructions can result in death, injury or property damage.

Top

Clearances to Combustibles

Top

 

 

Left

Right

Left

Right

Bottom

 

 

Bottom

 

 

 

Models 75 - 125

 

 

Models 150 - 400

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Models

 

75 - 125

150 - 400

 

 

 

 

 

Top

 

1"

6"

 

 

 

 

 

Bottom

 

1"

6"

 

 

 

 

 

Right

 

1"

31"*

 

 

 

 

 

Left

 

18"*

6"

 

 

 

 

 

Vent

 

2"

2"

 

 

 

* Clearance needed for servicing.

Roberts-Gordon LLC

Telephone: 716.852.4400

1250 William Street

P.O. Box 44

Fax: 716.852.0854

Buffalo, NY 14240-0044 USA

Toll Free: 800.828.7450

Installation Code and Annual Inspections:

All installation and service of ROBERTS GORDON® equipment must be performed by a contractor qualified in the installation and service of equipment sold and supplied by Roberts-Gordon and conform to all requirements set forth in the ROBERTS GORDON® manuals and all applicable governmental authorities pertaining to the installation, service and operation of the equipment. To help facilitate optimum performance and safety, Roberts-Gordon recommends that a qualified contractor conduct annual inspections of your ROBERTS GORDON® equipment and perform service where necessary, using only replacement parts sold and supplied by Roberts-Gordon.

For installations at elevations above 2000' (610 m), the appliance shall be derated 4% for each 1000' (305 m) of elevation above sea level.

Further Information:Applications, engineering and detailed guidance on systems design, installation and equipment performance is available through ROBERTS GORDON® representatives. Please contact us for any further information you may require, including the Installation, Operation and Service Manual.

This product is not for residential use.

© 2008 Roberts-Gordon LLC

www.rg-inc.com

Printed in U.S.A.

P/N 91039831

Page 54
Image 54
Roberts Gorden UHD[X][S][R] 75, UHD[X][S][R] 125 service manual Clearances to Combustibles