SECTION 11: USER INSTRUCTIONS
11.4.2 To Turn Heater Off
Set the thermostat to the "OFF" position. The burner will turn off immediately.
To restart, turn the thermostat above room temperature.
11.5 Simple Troubleshooting
Some possible reasons for the heater not operating are:
1.Gas supply not "ON".
2.Electricity supply not "ON".
3.The time and/or temperature controls are not "ON".
4.A limit switch may have operated. This may be caused by an interruption of the electrical supply, failure of the distribution fan or vent or heat exchanger blockage.
If a temperature limit switch persistently trips, there is a fault which must be investigated by a contractor qualified in the installation and service of
11.5.1 Simple Troubleshooting (Burner Faults)
If the burner fails to ignite for any reason, it will retry for ignition (four trials total). After four unsuccessful ignition trials, the control will put the heater into lockout for one hour.
Lockout should not occur during normal operation of the heater and indicates there is a fault condition which must be corrected. There is an LED light on the ignition control that flashes codes to assist in fault correction. See Page 27, Figure 16 for LED indication codes.
Figure 16: LED Diagnostic Codes
LED INDICATION | FAULT MODE |
|
|
Slow Flash | Normal Operation - No call for heat. |
|
|
Fast Flash | Normal Operation - Call for heat. |
|
|
2 Flashes | Ignition Lockout - No flame detected. |
|
|
3 Flashes | Airflow Fault - Pressure switch open or closed. |
|
|
4 Flashes | Temperature Limit or |
| Manual Reset Limit Switch Open |
|
|
5 Flashes | Flame Sense Error - Gas valve not energized. |
|
|
Steady On | Internal Control Failure |
|
|
27