13.4 Troubleshooting for Gas Valves

UHD LOW PROFILE DUCT FURNACE INSTALLATION OPERATION AND SERVICE MANUAL

13.4 Troubleshooting for Gas Valves

START

Is gas pressure at inlet of the valve correct for gas type?

Note pressure found.

Yes

Does gas pressure at outlet

of the valve rise when

valve turns on?

Yes

Does gas pressure at

outlet of valve return to zero or

lower when valve turns off?

Yes

No

No

No

Fault elsewhere.

Correct pressure problem.

Valve or ignition control

faulty. Replace with one of correct type.

Valve faulty.

Replace with one of

correct type.

Valve Operating

 

If problems persist, contact

No

Roberts-Gordon LLC at

TROUBLESHOOT ENDS.

 

www.rg-inc.com

 

 

13.5 Troubleshooting for Flue Blower

START

 

 

Does flue blower run

No

Correct power

automatically when there

supply problem.

is a call for heat?

 

 

 

 

 

Yes

 

 

Blower motor faulty.

 

 

Replace with correct type.

Yes

 

 

Does blower turn on and

 

Check blower motor leads

off while burner is firing

Yes

for loose connections.

continuously?

 

 

 

No

 

 

Blower Operating

 

If problems persist, contact

No

Roberts-Gordon LLC at

TROUBLESHOOT ENDS.

 

www.rg-inc.com

 

 

For optimum heater performance, use only replacement parts sold and supplied by Roberts-Gordon.

Conduct start-up procedure as shown on Page 23, Section 10.