23
5-2 Energy-Save Control and Peak Cut Control Click on [Functions 1] – [Peak Cut] in the menu to bring up the peak cut control sc reen, and mak e necessar y
peak cut settings to use the energy-save or peak cut control function.
Click [Save Settings] to send setting data to the AG-150A.
Note: Run the test run mode, and check that the equipment related to peak cut is connected properly to perform peak cut control.
(It is possible to perform control compulsorily by changing the control level.)
Note: The use of energy-save/peak cut control functions requires a separate license registration.
Confirm on the license registration screen (Ch8) that the license registration has been completed.
Note: If the user logs in as a building manager, some of the operations may be prohibited.
To enable peak cut, register the "Energy Saving (Peak Cut) " license to all AG-150A, and s et the peak cut
method and the indoor/outdoor units control method s. When the license is registered, the control can be
performed in 5 degrees (Level 0-4).
To enable energy saving control at the constant rate, register the "En ergy Saving" license to all AG-150A,
and set the level to "0" in [Indoor/Outdoor unit con trol method] section.
Save Settings
Send setting data to AG-150A
and PLC.
Refresh
Read setting data from
AG-150A and PLC.
Peak cut method
Select the peak cut method. Setting details
Set the details of the selected
method.
Indoor unit control method
Set the indoor unit control
method.
Outdoor unit control
method
Set the outdoor unit control
method.
AG-150A
Demand Controller Method
PI Controller
Up to 3 AG-150A can be
connected.
Up to 10 AG-150A can be connected.
PLC (with Electric
Amount Count Software) Pulse-method
watt-hour meter
AG-150A
Pulse
Electric Amount Count PLC Method
Demand level
report
PLC (with Electric
A
mount Count Software) Demand
Controller
Demand level
contact input
Pulse
Pulse
Notify the
control level
PLC etc
PI Controller Method
AG-150A
From external system Method
Remote AG-150A Method
Pulse-method
watt-hour meter
Pulse-method
watt-hour meter
Monitors electric
power
Monitors electric
power
Monitors
control level
AG-150A