32
6 Functions 2 6-1 Limiting the Set Temperature Operating Range
Click on [Function2]-[Set Temperature Range Limit] in the menu to open the set temperature range limit
screen, and make necessary settings to limit the set temper ature operating range of the local remote
controller.
Each user operation will be limited by setting t he lower limit and the up per limit of the set tem perature for
cooling operation, which leads to energy saving.
Note: The set temperature range can be limited on the following remote controllers. *1
ME remote controller (PAR-F27MEA-E) : Lower limit for cooling mode and upper limit for heating mode
ME remote controller (PAR-F27MEA-F) : Lower and upper limit for cooling, heating and automatic mode
Simple ME controller (PAC-SE51CRA-F) : Lower and upper limit for cooling, heating and automatic mode
MA remote controller (PAR-21MAA) *2 : Lower and upper limit for cooling, heating and automatic mode
Simple MA controller (PAC-YT51CRB) *2 : Lower and upper limit for cooling, heating and automatic mode
*1: The operation mode that can be set varies depending on the unit model.
*2: This function cannot be used depending on the indoor unit model.
Note: The set temperature range for all modes can be limited on the browser operation screen (for administrator), AG-150A
operation screen, and TG-2000A operation screen regardless of any settings being made. (The setting made on personal
browser operation screen is in effect on the personal screen.)
Note: If the user logs in as a building manager, some of the operations may be prohibited.
(1) Click the set temperature range display to display the
setting screen. Set the temperature range for cool ing,
heating and automatic mode.
Click [OK] to return the previous screen.
Note: When displayed in Fahrenheit, the temperature is
displayed in 2°F steps.
(2) Click [Save Settings] to send setting data to AG-150A.
Note: When copying settings of a group to another group, click [Copy] button. The screen will change to a selection screen
(yellow-green). Click [Paste] on a group to be copied.
Note: When setting all groups collectively, click [Batch operation] button, and input settings.
Save settings
Send setting data to AG-150A.
Refresh
Read setting data from AG-150A.
Batch operations
Click to set all groups
collectively.
Group No., group name
Group numbers and group
names will be displayed. Copy
Click to copy the settings.
Paste
Click to paste the settings.
Set temperature range
display
The set temperature range is
displayed.
Upper limit Lower limit