Checking code

Meaning, detecting method

 

 

Cause

Checking method & Countermeasure

 

 

 

 

 

 

1505

Suction

Judging that the state when the

Operation while neglecting to open

Once vacuum operation protection is

 

pressure

suction pressure reaches 0kg/

 

ball valve. Especially for the ball

commenced, do not attempt to

 

 

abnormality

cm2G (0MPa) during compressor

 

valve at low pressure side.

restart until taking the measures

 

 

 

operation indicates high pressure

 

At cooling

: Gas side ball valve

below.

 

 

 

 

 

 

by the discharge temperature and

 

At heating

: Liquid side ball valve

<Checking method>

 

 

 

 

low pressure saturation tempera-

When plural systems are existing,

• Check ball valve for neglecting to

 

 

ture, the back-up control by gas

 

the low pressure abruptly drop at

open.

 

 

 

 

 

 

bypassing will be conducted.

 

indoor stopping by the erroneous

• Check extended piping for

 

 

 

 

 

 

wiring of transmission line (differ-

clogging when ball valve is

 

 

 

 

 

 

ent connection of transmission line

opened.

 

 

 

 

 

 

 

 

and refrigerant piping).

• Check transmission line for errone-

 

 

 

 

Temporary vacuum condition due

ous wiring. (Confirm the correct wir-

 

 

 

 

 

to refrigerant distribution unbalance

ing and piping connection between

 

 

 

 

 

(insufficient refrigerant of low pres-

indoor and outdoor units by oper-

 

 

 

 

 

sure line) immediately after charg-

ating indoor unit one by one.)

 

 

 

 

 

ing refrigerant.

<Countermeasure>

 

 

 

 

 

 

 

 

 

• After checking with the above

 

 

 

 

 

 

 

method, make error reset by

 

 

 

 

 

 

 

 

power source reset.

 

 

 

 

 

 

 

 

 

• Then operate for 10~15-minutes

 

 

 

 

 

 

 

under the operation mode reverse

 

 

 

 

 

 

 

to that when the vacuum opera-

 

 

 

 

 

 

 

tion protection occurred (Heating

 

 

 

 

 

 

 

if error occurred in cooling, while

 

 

 

 

 

 

 

cooling if it occurred in heating),

 

 

 

 

 

 

 

and then enter into the ordinary

 

 

 

 

 

 

 

operation state.

 

 

 

 

 

 

 

 

 

2500

Leakage (water)

When drain sensor detects flood-

1)

Water leak due to humidifier or the

Check water leaking of humidifier

 

abnormality

ing during drain pump OFF.

 

like in trouble.

and clogging of drain pan.

 

 

 

 

 

 

 

 

2502

Drain pump

When indirect heater of drain sen-

1)

Drain sensor sinks in water be-

Check operations of drain pump.

 

abnormality

sor is turned on, rise in tempera-

 

cause drain water level rises due

 

 

 

 

 

 

 

ture is 20 deg. or less (in water) for

 

to drain water lifting-up mechanism

 

 

 

 

 

 

 

40 seconds, compared with the

 

trouble.

 

 

 

 

 

 

 

 

temperature detected before turn-

2)

Broken wire of indirect heater of

Measure resistance of indirect heater

 

 

ing on the indirect heater.

 

 

 

 

 

drain sensor.

of drain sensor.

 

 

 

 

 

 

 

 

 

 

(Normal: Approx. 82between 1-3 of

 

 

 

 

 

 

 

CN50)

 

 

 

 

 

 

 

 

3)

Detecting circuit (circuit board)

Indoor board trouble if no other

 

 

 

 

 

 

trouble.

 

problems is detected.

 

 

 

 

 

 

 

 

 

2503

Drain sensor

Short/open is detected during drain

1)

Thermistor trouble.

Check resistance of thermistor.

 

 

abnormality

pump operations. (Not detected

2)

Poor contact of connector.

0˚C

10˚C

: 9.7k

 

 

: 15k

 

 

 

when drain pump is not operating.)

 

(insufficient insertion)

20˚C

: 6.4k

30˚C

: 4.3k

 

 

Short

: 90˚C or more detected

3)

Full-broken of half-broken ther-

 

 

 

 

 

 

 

Open

: -40˚C or less detected

 

mistor wire.

 

 

 

 

 

 

 

 

 

 

4)

Indoor unit circuit board (detecting

Check contact of connector.

 

 

 

 

 

 

circuit) trouble.

Indoor port trouble if no other

 

 

 

 

 

 

 

 

problem is detected.

 

 

 

 

 

 

 

 

 

 

Operation of

When float switch operates (point

1)

Drain up input trouble.

Check drain pump operations.

 

 

float switch

of contact : OFF), error stop is ob-

2)

Poor contact of float switch circuit.

Check connect contact.

 

 

 

 

served with code No. “2503” dis-

 

 

 

 

played.

 

3)

Float switch trouble.

Check float switch operations.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

–110–

Page 112
Image 112
Mitsubishi Electronics P500YMF-C 110, Once vacuum operation protection is, Indoor and outdoor units by oper, Drain pump

PURY-P400, P500YMF-C specifications

Mitsubishi Electronics has long been a leader in the HVAC industry, known for its innovative technology and reliable performance. Among its notable offerings are the P500YMF-C and PURY-P400 models, designed to address the diverse needs of commercial and residential applications.

The Mitsubishi P500YMF-C is a high-performance outdoor unit that showcases energy efficiency and advanced refrigerant technology. It employs a sophisticated inverter-driven compressor, which optimizes energy usage by adjusting its speed based on the specific heating and cooling demands of the environment. This flexibility helps to minimize energy consumption while ensuring optimal comfort.

One of the standout features of the P500YMF-C is its ability to provide consistent heating and cooling even in extreme outdoor temperatures. The unit can operate effectively in low-temperature conditions, making it ideal for regions with harsh winters. Furthermore, the system is designed with a robust build, ensuring durability and longevity.

On the other hand, the PURY-P400 is an indoor multi-split system that complements the outdoor unit perfectly. It's designed for versatility and efficiency, capable of accommodating multiple indoor units connected to a single outdoor unit. This feature is particularly beneficial for larger spaces or buildings where different zones require individual climate control.

The PURY-P400 incorporates Mitsubishi's advanced filtration technology, which significantly improves indoor air quality. It features a multi-layer filtration system that effectively removes dust, allergens, and other particulates from the air, ensuring a healthier environment for occupants.

Both systems utilize R-32 refrigerant, which has a lower global warming potential compared to traditional refrigerants. This not only makes them more eco-friendly but also complies with emerging environmental regulations. The ease of installation and operation of these units is another noteworthy characteristic, with intuitive controls and user-friendly interfaces that facilitate seamless integration into existing systems.

In summary, the Mitsubishi P500YMF-C and PURY-P400 represent a fusion of technology, efficiency, and user-centric design. With a range of features aimed at enhancing performance and environmental sustainability, these models are an excellent choice for anyone looking to invest in a reliable and efficient HVAC system. Whether for residential or commercial use, Mitsubishi’s offerings continue to set the standard in comfort and efficiency.