Mitsubishi Electronics PURY-P400, P500YMF-C Dry operation, Thermostat on Inlet temp ˚C

Models: PURY-P400 P500YMF-C

1 148
Download 148 pages 51.35 Kb
Page 57
Image 57

(6) Dry operation

1.Indoor unit fan stop

2.Inverter output 0Hz

3.Indoor unit LEV, oil return LEV closed

4.Solenoid valve OFF

5.Outdoor unit fan stop

6.BC controller solenoid valve OFF

7.BC controller LEV fully closed

Dry operations

 

 

 

 

Normal operations

 

 

 

 

 

 

Thermostat ON

4-way valve OFF

 

 

 

 

 

 

 

 

 

Stop

 

 

 

 

 

 

YES

Test run start

 

Note : 2

 

 

 

 

 

 

 

 

 

 

 

Thermostat ON

 

 

NO

 

 

 

 

 

 

 

NO

Inlet temp. 18˚C

YES

Note : 1

1.Outdoor unit (Compressor) intermit- tent operations

2.Indoor unit fan intermittent opera- tionsYES

(Synchronized with compressor : low speed, OFF operations)

Note : 1

When indoor unit inlet temperature exceeds 18˚C, outdoor unit (compressor) and indoor unit fan start intermittent operations

 

synchronously. Operations of outdoor unit, BC controller, indoor unit LEV and solenoid valve accompanying compressor are

 

the same as those in cooling operations.

 

 

Note : 2

Thermostat is always kept on in test run, and indoor and outdoor unit intermittent operation (ON) time is a little longer than

 

normal operations.

 

 

–55–