94
No cooling
No heating
Check disconnection or looseness
of connectors.
Is there a problem?
Operate in cooling or heating (1 system
only when there are plural systems)
Cooling or heating
operation?
Heating operation
Note 1
Check if LEV 1 are fully open
LEV 1 fully open?
LEV3 are not
controlled
Check if LEV 1 are fully shut.
Yes
Note 2
No
Yes
No
Yes
No
Yes
No
Yes
Check if LEV3 is controlled by
superheat.
LEV3 is not controlled.
Check if SVM1 is ON.
SVM1 ON
Check if SVA, SVC are ON.
SVA, SVC ON
Check if SVB is OFF.
SVB OFF
Check if LEV 3 are controlled by
differential pressure.
Completion
Check SVB
Check SVA, SVC
Check SVM1
Check LEV3
Correct the problem.
Check LEV1
SVB ON
Check if SVB is ON.
SVA, SVC OFF
Check if SVA, SVC are OFF.
SVM1 OFF
Check if SVM1 is OFF.
LEV 1 fully shut?
Yes
No
Note 2
No
No
No
Yes
Yes
Yes
Note 3Note 3
No
Yes Yes
No

3) LEV, Solenoid Valve Troubleshooting Flow