VENT INSTALLATION

VENT INSTALLATION

WARNING

Horizontal sections of this vent system require a minimum of 3" clearances to combustibles at the top of the flue and 1" clearance at the sides and bottom until the flue penetrates the outside wall. A minimum 1" clearance all around the flue is acceptable at this point of penetration.

Vertical sections of this vent system require a minimum of 2" clearance to combustibles at the top of the unit directly above the stand-off. A minimum of 1" clearance all around the flue is acceptable thereafter.

A minimum of 3" clearance to the top is required along horizontal length until flue pipe penetrates outside wall.

A minimum 1"

clearance to combustibles permitted all around flue at outside wall

24" vertical rise required

before horizontal run

Figure 7 - Combustible Clearances for Vent Pipe

73D0024

13