Monessen Hearth KHLDV SERIES manual Installation For Vertical Termination, Vent Installation

Models: KHLDV SERIES

1 52
Download 52 pages 49.7 Kb
Page 21
Image 21
INSTALLATION FOR VERTICAL TERMINATION

VENT INSTALLATION

INSTALLATION FOR VERTICAL TERMINATION

1.Determine the route your vertical venting will take. If ceiling joist, roof rafters or other framing will obstruct the venting system, consider an offset. See Figure 20 to avoid cutting load bearing members.

For optimal flame appearance, a restrictor disk is necessary on straight vertical runs of 10' of more.

Runs may not incorporate elbows.

The disk is part number 56D3027 and is included in installation manual packet.

Drop the disk into a 5" inner collar before installing the first section of flue or install at the last section before installing the termination.

An additional disk may be installed on runs of 35' or more. Rotate disks perpendicular to each other.

NOTE: Pay special attention to these installation instructions for required clearances (air space) to combustibles when passing through ceilings, walls, roofs, enclosures, attic rafters, etc. Do not pack air spaces with insulation. Also note maximum vertical rise of the venting system and any maximum horizontal offset limitations. Offsets must fall within the parameters shown in Figures 19 and 20.

2.Set fireplace in desired location. Drop a line plumb down from the ceiling to the position of the flue exit. Mark the center point where the vent will penetrate the ceiling. Drill a small locating hole a this point.

Drop a plumb line from the inside of the roof to the ceiling locat- ing hole in the ceiling. Mark the center point where the vent will penetrate the roof. Drill a small locating hole at this point.

FLAT CEILING INSTALLATION

1.Cut a 101/2" (241mm) square hole in the ceiling using the locat- ing hole as a center point The opening should be framed to 101/2"x101/2" (241mm x 241mm) inside dimensions as shown in Figure 22 using framing lumber the same size as the ceiling joist. If the area above the ceiling is an insulated ceiling or a room, nail firestop from the top side. This prevents loose insula- tion from falling into the required clearance space. See Figure

21.Otherwise, install firestop below the framed hole. See Figure

2.Assemble the desired lengths of pipe and elbows necessary to reach from the burner system flue up through the firestop. Be sure pipe and elbow connections are fully twist-locked.

Roof

Flashing

Wall FLAT CEILING INSTALLATION

Strap

45° Elbows

Figure 20 - Offset with Wall Strap and 45° Ceiling Firstop

Figure 20 - Offset with Wall Strap and 45°

Elbows

Nails

Firestop

Figure 21 - If Area Above is a Room, Install Firestop above Framed Hole as Shown

1

/

2

"

10/

 

1

10

"

 

2

Nails Figure 22 - If Area Above is Not a Room, Install Firestop

Figure 22 - If Area Above is Not a Room, Install
Firestop above Framed Hole as Shown

73D0024

21

Page 21
Image 21
Monessen Hearth KHLDV SERIES manual Installation For Vertical Termination, Vent Installation, Flat Ceiling Installation