VENT INSTALLATION

INSTALLATION PLANNING

There are two basic types of direct-vent installation:

Horizontal Termination

Vertical Termination

It is important to select the proper length of vent pipe for the type of termination you choose. It is also important to note the wall thickness.

FOR HORIZONTAL TERMINATION

Select the amount of vertical rise desired. All horizontal run of venting must have 1/4" rise for every 12" of run towards the termination.

You may use up to three 90° elbows in this vent configuration. See Vertical/Horizontal Termination Configurations on pages 17 and 18.

FOR VERTICAL TERMINATION

WARNING

Never run the vent pipe level or downward. This may cause excessive temperatures which could cause a fire.

Measure the distance from the fireplace floor to the ceiling. Add the ceiling thickness, the vertical rise in an attic or second story, and allow for sufficient vent height above the roof line.

NOTE: You may use two 45° elbows in place of a 90° elbow. You must follow rise to run ratios when using 45° elbows. The appliance is approved for use with three 90° elbows maximum or a combination of 90° and 45° elbows up to a maximum of 270°.

For two-story applications, firestops are required at each floor level. If an offset is needed in the attic, additional pipe and elbows will be required.

You may use a chase with a vent termination with exposed pipe on the exterior of the house. See Installing A Vent System in an Outside Chase below. If pipe is enclosed in chase, it is not exposed.

It is very important that the venting system maintain its balance between the combustion air intake and the flue gas exhaust. Certain limitations apply to vent configurations and must be strictly followed.

INSTALLING A VENT SYSTEM IN AN OUTSIDE CHASE

A chase is a vertical boxlike structure built to enclose venting that runs along the outside of a building. A chase is required for such venting.

NOTICE NOTICE

Treatment of firestops and construction of the chase may vary from building type to building type. These instructions are not substitutes for the requirements of local building codes. You must follow all local building codes.

When installing in a chase, you should insulate the chase as you would the outside walls of your home. This is especially important in cold climates. Insulation should be considered a combustible material. Maintain proper clearances to all combustible materials.

14

73D0024

Page 14
Image 14
Monessen Hearth KHLDV SERIES manual Installation Planning, For Horizontal Termination, For Vertical Termination

KHLDV SERIES specifications

The Monessen Hearth KHLDV Series is a standout line of direct vent gas fireplaces designed to elevate both the aesthetics and functionality of residential spaces. Distinguished by their contemporary design and impressive heating capabilities, these units cater to homeowners seeking a modern solution for efficient warmth and ambiance.

One of the primary features of the KHLDV Series is its versatile design options. Available in various sizes and styles, these fireplaces can seamlessly integrate into diverse interior décor themes. The clean face design allows for a wide viewing area of the flames, providing an unobstructed view that enhances the overall experience. The elegant finish options, ranging from sleek black to decorative trim, make it easy for consumers to customize their unit to suit their personal style.

The KHLDV Series is also noted for its advanced heating technology. Utilizing direct venting, it ensures efficient operation while minimizing heat loss. This technology allows the fireplace to draw air from outside for combustion, which not only improves energy efficiency but also maintains optimal indoor air quality by preventing the depletion of oxygen in the living area. The balanced flue design further ensures that harmful gases are vented safely outside, giving homeowners peace of mind.

Control is another significant advantage of the KHLDV Series. Equipped with a multi-function remote control system, users can easily adjust the flame height and heat output to achieve their desired ambiance and comfort levels. This intuitive control system enhances the overall user experience, allowing homeowners to create a cozy environment with minimal effort.

Safety features are also a crucial consideration in the design of the KHLDV Series. Each unit comes with a built-in safety pilot system that ensures the fireplace operates reliably and safely, providing an additional layer of security for families. The high-quality materials used in construction further enhance durability, ensuring that the fireplace can withstand the test of time.

In summary, the Monessen Hearth KHLDV Series is a perfect blend of style, efficiency, and safety. With its sleek design, advanced heating technology, user-friendly control, and robust safety features, this series transforms any living space into a warm and inviting sanctuary. Ideal for modern homes, the KHLDV Series stands out as a compelling choice for those looking to enhance their home with a functional and elegant fireplace.