Monessen Hearth KHLDV SERIES manual Only persons licensed to work with, Fireplace Installation

Models: KHLDV SERIES

1 52
Download 52 pages 49.7 Kb
Page 24
Image 24
Only persons licensed to work with

FIREPLACE INSTALLATION

WARNING

Only persons licensed to work with

 

 

gas piping may make the necessary

 

gas connections to this appliance.

 

 

CAUTION

Amanual shutoff valve must be installed upstream of the appliance. Union tee and plugged 1/8" NPT pressure tapping point should be installed upstream of the appliance. See Figure 24.

NOTE : The gas line connection may be made using 1/2" rigid tubing or an approved flex connector. Since some municipalities have additional local codes it is always best to consult your local authorities and the current edition of the National Fuel Gas Code ANSI.Z223.1, NFPA54. In Canada CAN/CGA-B149 (1 or 2) Installation Code.

A listed manual shutoff valve must be installed upstream of the appliance. Union tee and plugged 1/8" NPT pressure tapping point should be installed upstream of the appliance. See Figure 24.

IMPORTANT: Install main gas valve (equipment shutoff valve) in an accessible location. The main gas valve is for turning on or shutting off the gas to the fireplace.

Check your building codes for any special requirements for locating equipment shutoff valve to fireplaces.

Apply pipe joint sealant lightly to male threads. This will prevent excess sealant from going into pipe. Excess sealant in pipe could result in clogged burner system valves.

CAUTION

Use pipe joint sealant that is resistant to liquid petroleum (LP) gas.

We recommend that you install a sediment trap/drip leg in supply line as shown in Figure 24. Locate sediment trap/drip leg where it is within reach for cleaning. Install in piping system between fuel supply and burner system. Locate sediment trap/drip leg where trapped matter is not likely to freeze. A sediment trap collects moisture and contaminants and keeps them from going into the burner system gas controls. If sediment trap/drip leg is not installed or is installed wrong, burner system may not run properly.

CSA Design-Certified Equipment

Shutoff Valve with 1/8" NPT Tap*

Approved Flexible

Gas Line

Sediment Trap/Drip Leg

 

Natural Gas

 

From Gas Meter

Tee Joint

(4.5" W.C. to 10.5" W.C. Pressure)

Propane/LP

Pipe Nipple

From External Regulator

Cap

(11" W.C. to 13" W.C. Pressure)

 

Figure 24 - Gas Connection

24

73D0024

Page 24
Image 24
Monessen Hearth KHLDV SERIES Only persons licensed to work with, gas piping may make the necessary, Fireplace Installation