VERTICAL (THROUGH-THE-ROOF)

VENT INSTALLATION

VERTICAL (THROUGH-THE-ROOF)

APPLICATIONS

This gas fireplace has been approved for,

Vertical installations up to 40' (12m) in height. Up to a 10' (3m) horizontal vent run can be installed within the vent system using a maximum of two 90° elbows. See Figure 18.

NOTE: Horizontal sections of this vent system require a minimum of 3" clearances to combustibles at the top of the flue and 1" clearance at the sides and bottom until the flue penetrates the outside wall. A minimum 1" clearance all around the flue is acceptable at this point of penetration.

Vertical sections of this vent system require a minimum of 1" clearance to combustibles on all sides of the pipe.

Up to two 45° elbows may be used within the horizontal run. For each 45° elbow used on the horizontal plane, the maximum horizontal length must be reduced by 18" (450mm).

Example: Maximum horizontal length No elbows = 10’ (3m)

1x45° elbows = 8.5’ (2.6m) 2x45° elbows = 7’ (2.1m)

A minimum of an 8' (2.5m) vertical rise is required.

Two sets of 45°elbows offsets may be used within the vertical sections. From 0 to a maximum of 8' (2.5 m) of vent pipe can be used between elbows. See Figure 19.

The maximum angular variation allowed in the system is 270°. See Figure 19.

The minimum height of the vent above the highest point of penetration through the roof is 2' (610mm).

Example:

Elbow 1

=

90°

 

Elbow 2

=

45°

 

Elbow 3

=

45°

 

Elbow 4

=

90°

Total Angular Variation

=

270°

40' Maximum Height

12' Minimum Height

10'

Maximum

24" Min.

Support Straps

Every 3'

Figure 18 - Support Straps for

Horizontal Runs

 

1

 

2

 

3

24" Min.

4

 

Figure 19 - Maximum Elbow Usage