Multiquip operation manual BLW-400SSW PRE-SETUP, General Inspection Prior to Operation

Models: BLW-400SSW

1 138
Download 138 pages 39.29 Kb
Page 27
Image 27

Table of Contents

BLW-400SSWPRE-SETUP

General Inspection Prior to Operation

The BLW-400SSW utilizes a welder/AC generator that has been thoroughly inspected and accepted prior to shipment from the factory. However, be sure to check for damaged parts or components, or loose nuts and bolts, which could have occurred in transit.

Ground

The nut and ground terminal on the welder/AC generator should always be used to connect to a suitable ground. The ground path should be of #8 size wire.

Connect the terminal of the ground wire between the lock washer and the nut and tighten the nut fully. Connect their end of the wire to a suitable ground.

Circuit Breakers

To protect the welder/AC generator from an overload, a 3-pole, 53 amp, main circuit breaker is provided. In addition 2-two pole, 25 amp breaker is provided for the G.F.C.I. receptacles. Make sure to switch both circuit breakers to the "OFF" position prior to starting the engine.

Extension Cable

When electric power is to be provided to various tools or loads at some distance from the welder/AC generator, extension cords are normally used. Cables should be sized to allow for distance in length and amperage so that the voltage drop between the welder/AC generator and point of use (load) is held to a minimum. Use the cable selection chart (Table 7 ) as a guide for selecting proper cable size.

Table 7. Cable Selection (60 Hz, Single Phase Operation)

Current in

Load In Watts

 

 

Maximum Allowable Cable Length

 

 

 

 

 

 

 

 

 

 

 

At 120

At 240

 

 

 

 

 

 

 

 

Amperes

#10 Wire

 

#12 Wire

#14 Wire

 

#16 Wire

 

Volts

Volts

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2.5

300

600

1000 ft.

 

600

ft.

375 ft.

 

250 ft.

 

 

 

 

 

 

 

 

 

 

 

5

600

1200

500

ft.

 

300

ft.

200 ft.

 

125 ft.

 

 

 

 

 

 

 

 

 

 

 

7.5

900

1800

350

ft.

 

200

ft.

125 ft.

 

100 ft.

 

 

 

 

 

 

 

 

 

 

10

1200

2400

250

ft.

 

150 ft.

100 ft.

 

 

 

 

 

 

 

 

 

 

 

15

1800

3600

150 ft.

 

100 ft.

65 ft.

 

 

 

 

 

 

 

 

 

 

 

20

2400

4800

125 ft.

 

75 ft.

50 ft.

 

 

 

 

 

 

 

 

 

 

 

CAUTION: Equipment damage can result from low voltage.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BLW-400SSW-WELDER/AC GENERATOR— PARTS & OPERATION MANUAL— REV. #1 (06/15/01) — PAGE 27