Multiquip DCA-220SSVU— GENERATOR OUTPUTS/ GAUGE READING, Maximum Amps, Change-OverSwitch

Models: DCA-220SSVU

1 86
Download 86 pages 53.52 Kb
Page 29
Image 29
DCA-220SSVU — GENERATOR OUTPUTS/ GAUGE READING

DCA-220SSVU — GENERATOR OUTPUTS/ GAUGE READING

Maximum Amps

Table 10 shows the maximum amps the generator can pro- vide. DO NOT exceed the maximum amps as listed.

Table 10. Generator Maximum Amps

Model
DCA220SSVU

 

 

Rated Voltage

Maximum Amps

 

 

Single Phase

488.9 amps (4 wire)

120 Volt

 

 

 

Single Phase

244.4 amps (4 wire)

240 Volt

 

 

 

Three Phase

529 amps

240 Volt

 

 

 

Three Phase

264 amps

480 Volt

 

 

 

Figure 17. AC Voltmeter

Figure 18. AC Voltmeter Gauge

Change-Over Switch

(Volt reading on W-U Lug)

How to Read the Output Terminal Gauge.

The AC ammeter and AC voltmeter change-over switches on the control panel DO NOT effect the generator output. They are provided to help observe how much power is being supplied, produced at the UVWO terminals lugs.

When the voltage change-over board is jumpered for 3Ø, 240V operation (See Figures 17 and18), place the AC Volt- meter Change-Over Switch (See Figures 19 and 20) to the W-U position and the AC Ammeter Change-Over Switch (Figure 19) to the U or W position to read the output on the selected leg.

Figure 19. AC Ammeter

Change-Over Switch

NOTE

Figure 20. AC Ammeter (Amp reading on U lug)

The ammeter gauge will only show a reading when the Output Terminal Lugs are connected to a load and in use.

Figure 16. Voltage Change-Over Board 240V Configuration

DCA-220SSVU— OPERATION AND PARTS MANUAL — REV. #1 (01/20/06) — PAGE 29

Page 29
Image 29
Multiquip DCA-220SSVU— GENERATOR OUTPUTS/ GAUGE READING, Maximum Amps, How to Read the Output Terminal Gauge, Model