DCA-220SSVU — GENERATOR OUTPUTS

DCA-220SSVU — GENERATOR OUTPUTS

Generator OutputVoltages

A wide range of voltages are available to supply voltage for many different applications. Voltages are selected by apply- ing jumpers (6) to the voltage change-over board (Figure 15). To obtain some of the voltages as listed in Table 6 (see below) will require a fine adjustment using the voltage regu- lator (VR) control knob located on the control panel.

Voltage Change-Over Board

The voltage change-over board (Figure 15) is located on the control box, behind the generator control panel. This board has been provided for ease of voltage selection.

Generator Amperage

Tables 8 and 9 describe the generator’s current output capa- bility for both 1Ø-phase and 3Ø phase applications.

Table 8. Generator Ampere Ratings 1

kW

120V

139V

240V

277V

480V

 

 

 

 

 

 

16

44

38

22

19

11

 

 

 

 

 

 

36

155

86

78

43

25

 

 

 

 

 

 

56

466

134

233

67

39

 

 

 

 

 

 

76

210

182

105

82

53

 

 

 

 

 

 

96

266

230

133

115

67

 

 

 

 

 

 

116

322

278

161

139

80

 

 

 

 

 

 

136

378

326

189

163

94

 

 

 

 

 

 

156

433

374

216

187

108

 

 

 

 

 

 

176 (Max)

488.6

422

244.3

211

122

 

 

 

 

 

 

These calculations refelect the maximum amount of current the generator can provide at each output terminal pair. To obtain the total generator amperage multiply by 3.

Example 1: 488.6 amps @ 120V per output terminal pair X 3 =1,486 amps

Example 2: 244.3 amps @ 240V per output terminal pair X 3 =733 amps

Figure 15. Voltage Change-Over Board
CAUTION - CHANGINGVOLTAGES

NEVER attempt to place jumper plates on the voltage change-over board while the generator is in operation. There exist the possibility of electrocution, electrical shock or burn, which can cause severe bodily harm or even death!

Table 7. Voltages Available

Three Phase

208V

220V

240V

416V

440V

480V

(Switchable)

 

 

 

 

 

 

 

 

 

 

 

 

 

Single Phase

120V

127V

139V

240V

254V

277V

(Switchable)

 

 

 

 

 

 

 

 

 

 

 

 

 

Table 9. Generator Ampere Ratings 3

KW

240V480V

 

 

 

20

48

24

 

 

 

40

96

48

 

 

 

60

144

72

 

 

 

80

192

96

 

 

 

100

240

120

 

 

 

120

288

144

 

 

 

140

337

168

 

 

 

160

385

192

 

 

 

180

433

216

 

 

 

200

481

241

 

 

 

220

529

264

 

 

 