DCA-300SSK SERIES — GEN. START-UP PROCEDURE (MANUAL)

DCA-300SSK SERIES — GEN. START-UP PROCEDURE (MANUAL)

BEFORE STARTING (S/N 3701673 and below)

1. Place the main,G.F.C.I. and aux. circuit breakers (Figure 42)

 

in the “OFF” position prior to starting the engine.

Steps 1 thru 20 are referenced

for Engine Operating Panel

S/N

NOTE

3701673 and below. See Figure

 

 

40 below. This unit has an igni-

 

tion switch and a throttle

 

handle.

Figure 40. Engine Operating Panel

S/N 3701673 and Below

CAUTION - LETHAL EXHAUST HAZARD

The engine's exhaust contains harmful emissions.

ALWAYS have adequate ventilation when operating.

Direct exhaust away from nearby personnel.

WARNING - STARTINGTHE GENERATOR

NEVER! manually start the engine with the main, GFCI or auxiliary circuit breakers in the ON (closed) position.

Figure 42. Main, Aux. and GFCI

Circuit Breakers (OFF)

2.Make sure the the voltage change-over board has been configured for the desired output voltage.

3.Connect the load to the UVWO terminals or auxiliary receptacles as shown in Figure 12. These load connection points can be found on the output terminal panel. To gain access to the UVWO terminals or other power receptacles, unlock the access cover and lift the door.

4.Tighten terminal nuts securely to prevent load wires from slipping out

5.Close all engine enclosure doors (Figure 42).

Figure 42. Engine Enclosure Doors

DCA-300SSK SERIES — PARTS AND OPERATION MANUAL (STD)— REV. #4 (03/27/06) — PAGE 37