120VAC GFCI Receptacles

DCA-300SSK SERIES — OUTPUT TERMINAL PANEL FAMILIARIZATION

120VAC GFCI Receptacles

There are two 120 VAC, 20 amp GFCI (Duplex Nema 5-20R) recepacles provided on the output terminal panel. These receptacles can be accessed in any voltage change-over board position. Each receptacle is protected by a 20 amp circuit breaker. These breakers are located directly above the GFCI receptacles. Remember the load output (current) of both GFCI receptacles is dependent on the load requirements of the UVWO terminals.

Pressing the reset button resets the GFCI receptacle after being tripped. Pressing the "Test Button" (See Figure 9) in the center of the receptacle will check the GFCI function. Both receptacles should be tested at least once a month.

Each auxiliary receptacle is protected by a 50 amp circuit breaker.These breakers are located directly above the GFCI receptacles. Remember the load output (current) on all three receptacles is dependent on the load requirements of the UVWO terminals.

Turn the voltage regulator control knob (Figure 11) on the control panel to obtain the desired voltage.Turning the knob clockwise will increase the voltage, turning the knob counter- clockwise will decrease the voltage.

Figure 11. Voltage Regulator Control Knob

Figure 9. G.F.C.I. Receptacle

Twist Lock Dual Voltage 240/139 VAC Receptacles There are three 240/139 VAC, 50 amp auxiliary twist-lock(CS-6369) receptacles (Figure 10) provided on the output terminal panel. These receptacles can be accessed in any voltage change-over board position.

Figure 10. 240/139 VAC Twist-Lock

Auxiliary Receptacles